Directory · Phoenix
Phoenix commercial kitchen hood cleaning
Research index for operators. Public rules we found, how to vet a cleaner, open listing slots. Not a ranked vendor list.
What operators usually get asked
- Phoenix adopted the 2024 International Fire Code (with amendments), effective February 17, 2026. Fire Prevention contact published on the city Fire Code page: 602-262-6771 / fireprevention.pfd@phoenix.gov (verify current).
- Phoenix Fire Code §606 Table 606.3.3.1 inspection frequencies: solid fuel 1 month; high-volume (24-hour / charbroil / wok) 3 months; all other 6 months; low-volume 12 months.
- If grease accumulation is found, clean per ANSI/IKECA C10; keep inspection/cleaning records and conspicuous tags. That is the grease-clean track. Suppression service is separate.
- Your cleaner has to file the cleaning report with Phoenix Fire Prevention through The Compliance Engine within 30 days, pass or fail. A deficient report gets a fire inspector assigned to follow up with you (details below).
- Confirm Phoenix amendments in the official packet on the Fire Code page before treating a vendor paraphrase as law.
- These rules cover the City of Phoenix. Scottsdale, Tempe, Mesa, Glendale, Chandler and the other Valley cities run their own fire departments; ask the local fire marshal which code edition and report system apply there. Mesa and Scottsdale notes are below.
Inspection intervals (Phoenix Fire Code Table 606.3.3.1)
| Type of cooking operation | Inspect at least every |
|---|---|
| Solid fuel-burning cooking appliances | 1 month |
| High-volume: 24-hour, charbroiling, wok | 3 months |
| All other cooking operations | 6 months |
| Low-volume: places of worship, seasonal, senior centers | 12 months |
Or as approved by the fire code official. See how often to inspect.
Fire Marshal policy: hoods in schools, daycares, and care facilities
The Phoenix Fire Prevention 2026 Explanatory Policy Manual has a policy on kitchen hood maintenance in Group E, I-1, I-2, I-4, and college R-2 buildings (schools, daycares, assisted living, nursing homes, dorms). The parts that matter to a kitchen manager:
- Type I hoods follow Table 606.3.3.1: every 6 months for normal use, annually for light use such as religious facilities and senior centers. Daycare and educational facilities are inspected every 6 months.
- An unused Type I hood is not off the hook. If the operator stops grease-producing cooking, the hood and suppression system must still be maintained, or removed.
- Type II hoods (dishwashers, ovens, steam tables with no grease or smoke) don’t need suppression and should not build up grease. Noticeable grease buildup can lead to a Type I requirement.
Related: school and cafeteria schedules and senior living dining kitchens.
Reinspection and hood permit fees
The Phoenix Fire Prevention Fee Schedule (effective 1/20/2026) lists a reinspection fee of minimum $195 (1 hour) that may be assessed when corrections aren’t made, items from the first inspection are still open at reinspection, access isn’t provided at the scheduled time, or additional inspections are required. Installing an automatic extinguishing hood carries separate plan review and inspection fees (minimum $390 plan review; minimum $292.50 inspection per the schedule). Those are suppression install fees, not hood cleaning fees. See reinspection fees and what a reinspection notice usually cites.
Your cleaning report goes to Phoenix Fire (The Compliance Engine)
Phoenix Fire Code §110.3 lets the fire code official require that certain records be filed with the department. The Fire Marshal’s Compliance Engine Recordkeeping policy (2026 Explanatory Policy Manual, updated 04/01/2026) uses it for hood work:
- Commercial kitchen exhaust cleaning and hood suppression system reports are both on the list of reports that must be submitted.
- The contractor submits a copy to Fire Prevention within 30 days of finishing the job, whether the system passed or not. Correction reports for deficient systems are also due within 30 days of the repair.
- Submittals go only through thecomplianceengine.com. A report emailed or mailed to the department does not count.
- Each kitchen hood is submitted on its own, cleaning reports included. A kitchen with three hoods should end up with three entries, not one lumped report.
- Separate buildings at one address each get their own premise in the system.
What happens next, per the Phoenix Fire ITM program page: once a report is in, a Fire Inspection staff member reviews it and contacts the premises responsible party. Repairs to fire protection systems found deficient may need an FITM permit from Phoenix Fire (150 S. 12th St.); the inspector tells you which permit applies, and you tell the repair contractor. Phoenix has used The Compliance Engine (run by BRYCER) since December 1, 2019.
Filing fee: BRYCER says service providers, not fire departments, pay a per-system report fee. The Phoenix amount is Unknown to us. Ask the cleaner whether it is in the quote or billed on top. ITM questions: PFD.ITM@Phoenix.gov. See digital vs paper certificates.
Operating permits when you buy or take over a kitchen
- The 2026 Explanatory Policy Manual says Phoenix operating permits are not transferable. Any change in occupancy, operation, use, hazard, tenancy, or ownership requires a new permit.
- Permits a restaurant may hold, from the same manual and the 1/20/2026 fee schedule: Places of assembly (F162, expires after 1 year, minimum $195); Open flames or candles in dining areas (F189, 1 year, minimum $195); Mobile food preparation vehicles (F461, 3 years, minimum $195). Whether your dining room needs a place-of-assembly permit depends on its occupancy; ask Fire Prevention at 602-262-6771.
- Operating or starting work without a required Fire Prevention permit can draw a fee of 300% of the permit and inspection fees.
See buying or taking over a restaurant.
Mesa, Scottsdale, Glendale, Chandler and the West Valley districts: different paperwork
The hood cleaning standard is the same across the Valley (cleaned when grease is found, by a qualified company, with a report and a tag). What changes from city to city is the permit you hold and where the cleaning report has to go. What each department publishes:
- Mesa (Mesa Fire and Medical). Every occupancy except one- and two-family homes and home businesses needs an annual Fire Safety Operational Permit (FSOP), one per location, filed and renewed in the city’s DIMES portal. The FSOP expires at the end of the month printed on it, and Mesa does not mail a paper copy. Fire inspections are generally not scheduled in advance. Mesa lists fast food and smaller restaurants as medium risk (inspected every two years), and assembly occupancies, hotels and hospitals as high risk (annual). Fire protection contractors register with Mesa and handle system deficiencies through DIMES. Questions: fireprevention@mesaaz.gov, 480-644-2622.
- Scottsdale (Scottsdale Fire). Scottsdale tracks fire protection system reports in BRYCER’s Compliance Engine. Its adopted FY 2026/27 fee schedule (Resolution 12788) lists a $35 Fire Protection System Compliance Reporting Fee, a $200 re-inspection fee, and $700 for after-hours and weekend fire inspections. The city’s FY 2025/26 fee notice described the reporting line as the Brycer Compliance Engine charge, collected per system upload. Expect your cleaner or suppression company to pass it through, and ask whether the quote includes it.
- Buckeye Valley, North County and South County fire districts (Arizona Fire & Medical Authority). Contractors must submit every report, compliant or not, through The Compliance Engine, and the Authority lists commercial kitchen hood suppression systems (testing and cleaning) among the tracked systems. Questions: 623-544-5400.
- Glendale (Glendale Fire). City Council Resolution R24-20 (March 26, 2024) authorized an agreement with Brycer for The Compliance Engine, which the department uses as its inspection, test and maintenance database. The signed agreement runs three years from April 1, 2024 and renews automatically. Brycer collects the filing fees from the service contractors, splits them with the city, and sends the reminder notices and overdue calls. The agreement does not list a fee amount or the system types tracked, so ask your cleaner whether your hood report goes into The Compliance Engine and whether the filing fee is in the quote.
- Chandler (Chandler Fire). Anyone who inspects, tests or maintains a fire protection system in Chandler, including wet chemical hood suppression, must hold an Arizona license and be on the Chandler Fire Department Approved Fire Protection Contractors list (FD Form 707). For wet and dry chemical work the city accepts C-16, CR-16 or R-16 licenses. The permit costs $85 a year, requires a liability certificate naming Chandler Fire as additional insured, and the list expires December 31, so contractors re-apply each January. Chandler also asks contractors to leave a copy of the service report with the business. We found no Chandler rule on online filing of hood cleaning reports. Questions: 480-782-2120.
- Tempe, Gilbert and the rest. Tempe enforces the 2024 International Fire Code with local amendments and takes operational permit applications online. We have not confirmed whether Tempe, Gilbert or the other Valley departments require online filing of hood cleaning reports. Call Fire Prevention before the job and ask, so your cleaner knows where the report goes.
Moving between cities matters too: a Phoenix operating permit and a Mesa FSOP are separate permits from separate departments, so a second location in another city starts its own permit file.
Hood wash water and the grease interceptor
Phoenix Water Services runs the commercial FOG inspection program under City Code Chapter 28. It is a separate program from the fire code, but hood day touches it:
- Every food service establishment that prepares food on site must have a grease interceptor (Phoenix FOG BMP manual). Indoor hydromechanical units are allowed for up to four fixtures; more than four fixtures, or any dishwasher or disposal, requires an outdoor gravity interceptor.
- The Phoenix Plumbing Code (2024) lists automatic hood wash units among the fixtures that must drain to a grease interceptor.
- City Code §28-15: gravity interceptors at food service establishments must be fully pumped and cleaned at least every three months and before solids and grease pass 25% of liquid capacity; hydromechanical interceptors at least every 30 days, never more than 90 days.
- Keep pumping, volume, disposal, and repair records on site for three years.
- Chemicals, enzymes, bacteria, solvents, or emulsifiers used to dissolve FOG instead of physical cleaning are prohibited. Ask your hood cleaner how their degreaser rinse is captured.
See chemical runoff and grease waste and grease trap service on hood day.
Before you call for a quote
- Pick your cooking volume from the table above: 1 month solid fuel, 3 months high-volume (24-hour, charbroil, wok), 6 months typical, 12 months low-volume.
- Read the date and company off the service tag on the hood and find the last report. Grease load is one of the main things that moves a quote (see what drives quote variance).
- Say why you are calling: a Phoenix Fire inspection or deficiency follow-up, a health inspection, an insurer, a landlord, or a new owner. If a fire inspector already contacted you, have the deficiency notice ready.
- Count hoods. Phoenix wants each hood filed separately, so the quote and the report should list them one by one.
- Describe the roof: fan location, roof hatch or ladder, and any limits on when the crew can be on the roof or in the kitchen. Confirm after-hours access before booking (see after-hours premiums).
- Ask the cleaner to confirm they submit to The Compliance Engine within 30 days, whether the filing fee is included, and that you get your own copy with before-and-after photos.
- Ask where the wash water goes. It belongs in the grease interceptor, and hood wash units must drain there under the Phoenix Plumbing Code.
- Outside the City of Phoenix, tell the cleaner which fire department you fall under. Scottsdale and the West Valley fire districts use The Compliance Engine too; in Mesa, have your FSOP number from DIMES ready.
- In Chandler, ask your suppression company to confirm it is on this year’s Chandler Fire approved contractor list before it services the system. The list resets every December 31.
- Have your suppression company’s last service date handy. Phoenix Fire’s inspection frequency chart (compiled 2018) lists contractor inspection of hood suppression every 6 months.
Request quotes from Phoenix hood cleaners below.
Vet checklist
- Certs your AHJ accepts (IKECA or local equivalent): ask, then verify
- Certificate of insurance before they arrive
- Photo report: plenum, ducts, rooftop fan, not only the canopy
- Full-system vs canopy wipe in writing
- After-hours and roof access confirmed before the crew shows up
- Wash water plan: captured and routed to the interceptor, nothing to the lot or storm drain
- Tag on the hood with provider name, address, phone, and service date
Open listing slots
Sources
- Phoenix Fire Code page (2024 IFC effective 2026-02-17; amendment packet; fee schedule; contact)
- Phoenix IFC 2024 Ch. 6 (UpCodes)
- Phoenix Fire Prevention: 2026 Explanatory Policy Manual (PDF) (Kitchen Hood Maintenance and Protection policy; Compliance Engine Recordkeeping policy; operating permit expiration table)
- Phoenix Fire Prevention Fee Schedule, effective 1/20/2026 (PDF) (reinspection; automatic hood plan review and inspection; operating permit minimums; 300% unpermitted-work fee)
- Phoenix City Code §28-15, Interceptors: Maintenance
- Phoenix Water Services: FOG Best Management Practices for Food Service Establishments (PDF)
- Phoenix Fire: Inspections, Testing, and Maintenance (The Compliance Engine since 12/1/2019; inspector follow-up; FITM permit; contacts)
- Phoenix Fire: Fire Protection System Inspection Frequency Chart (PDF, compiled 2018) (hood suppression semiannual inspection)
- BRYCER: The Compliance Engine (service providers pay a per-system report fee)
- Phoenix Plumbing Code 2024, Ch. 10 (UpCodes) (hood wash units drain to grease interceptor)
- City of Mesa: Fire Business Services (annual FSOPs in DIMES; risk-based inspection frequency; third-party contractor registration)
- Scottsdale Fire Department Fees & Charges Schedule, adopted FY 26/27 (PDF) (compliance reporting $35; re-inspection $200; after-hours inspection $700)
- City of Scottsdale: FY 2025/26 proposed new fees and fee increases (PDF) (Brycer Compliance Engine fee per upload)
- Arizona Fire & Medical Authority: Code Enforcement (Compliance Engine reporting incl. kitchen hood suppression testing and cleaning)
- City of Glendale: Resolution R24-20, agreement with Brycer for The Compliance Engine (March 26, 2024, PDF)
- City of Glendale and Brycer: signed service agreement (term from April 1, 2024; fee collection and notices, PDF)
- City of Chandler: Fire Protection Contractor Permit ($85, approved list expires December 31)
- City of Tempe: Fire Inspections (2024 IFC with Tempe amendments, operational permits)
Related guides
- How often to inspect
- Full-system vs canopy wipe
- What your report must show
- Opening a new restaurant: first clean and inspection timing
- Quote checklist
- What a full-system clean includes
- Austin · Denver
Request a listing: company, metro, certs, insurance, service area, photo-report policy.
Get quotes from local hood cleaners
Tell us about your kitchen and we'll pass the request to up to 3 local providers in Phoenix. No cost to you, no obligation.