Directory · Denver
Denver commercial kitchen hood cleaning
Research index for operators. Public rules we found, how to vet a cleaner, open listing slots. Not a ranked vendor list.
What code applies
- Denver adopted the 2024 I-codes on June 13, 2025, including the 2024 International Fire Code as the 2025 Denver Fire Code. The adopting ordinance makes the 2025 codes effective December 31, 2025; fire permit applications submitted between June 13 and December 31, 2025 could still use the 2022 code.
- Denver’s amendments to Chapter 6 deal with elevators (§604). We found no Denver amendment to the commercial kitchen hood section, so the model §606.3.3 text applies as published.
- Fire Prevention Division: 745 W. Colfax Avenue, 720-913-3474, denfpb@denvergov.org. Business license inspection requests: 720-913-3409.
Inspection intervals (Denver Fire Code Table 606.3.3.1)
| Type of cooking operation | Inspect at least every |
|---|---|
| Solid fuel-burning cooking appliances | 1 month |
| High-volume: 24-hour, charbroiling, wok | 3 months |
| All other cooking operations | 6 months |
| Low-volume: places of worship, seasonal, senior centers | 12 months |
- Or as approved by the fire code official. Inspections by qualified individuals (§606.3.3.1).
- Grease found means cleaning to ANSI/IKECA C10 (§606.3.3.2).
- Records name the individual and company, describe the inspection, and give the date; cleaning records name who cleaned and when (§606.3.3.3).
- A tag with the provider’s name, address, phone, and service date goes in a conspicuous spot; prior tags are covered or removed (§606.3.3.3.1).
- Suppression service is a separate requirement (§606.3.4, pointing to §904.14.5).
Changing the menu can change your row. See changing your menu or equipment and how often to inspect.
Who is licensed for what
- The Denver Fire Code (§116) requires Denver Fire Department licenses for design, installation, inspection, and testing of life safety systems. The list includes Commercial Kitchen Hood and Commercial Kitchen Hood/Extinguisher.
- DFD says contractors who inspect hood suppression systems must hold a Denver Fire License for Commercial Kitchen Hoods and Fire Extinguishers. Journeyman applicants need a CSA ID card; the license is $150 for a three-year cycle per the DFD application.
- Those are suppression licenses. We found no separate DFD license category for hood and duct cleaning. Ask your cleaner which certification they hold (IKECA certification) and ask your suppression company for its DFD license number.
Inspections and fees (2026)
DFD fire safety inspections of commercial occupancies happen once a year (marijuana facilities twice). Inspection and permit fees went up effective July 1, 2026, the first change since 2009. Dollar amounts below come from the DFD Inspection Fee Schedule dated July 23, 2026 and the plan-review / systems-testing page — confirm before you budget.
| Line | Published amount |
|---|---|
| Company (firehouse) annual inspection — examples by size | $75 (2,000 sq ft); $105 (6,000); $120 (10,000); schedule also uses a $3.12 / 1,000 sq ft adder on mid bands |
| Assembly occupancy (Fire Prevention inspector) — A2 / A2.1 / A4 | $165 (occupant load 300–500); $245 (501–1,000); $325 (1,001–5,000) |
| Non-compliance reinspection | $85 first; $165 each subsequent |
| Fire system acceptance-test reinspection (permitted work) | $500 first; $800 each subsequent |
| After-hours systems inspection | $100 / hour / inspector (minimum may apply for standby) |
- DFD’s undated public Inspection Checklist has a Commercial Cooking block: hood suppression inspected every 6 months and after an activation; hood cleaning records available; Type I hood required / cleaning required when applicable; Class K extinguisher wherever there is grease production. That checklist is what a company or Fire Prevention walk often looks for on the cooking line — separate from the Table 606.3.3.1 exhaust-inspection intervals above.
- An inspection report with violations comes with an invoice; reinspections also get a report and invoice. Pay through E-Permits. See what a reinspection notice usually cites and reinspection fees.
- Unknown on this page: a single published “restaurant kitchen” annual-inspection flat fee that always applies (most kitchens fall under the company square-footage table or an assembly band by occupant load). Confirm the line on your own invoice with Fire Prevention at 720-913-3474.
New hoods, remodels, and equipment changes
- Restaurant projects go through E-permits as a “building log,” which starts building, health, sewer use and drainage, and fire reviews at the same time. Smaller projects, such as upgrading kitchen appliances, may need only some of those reviews.
- CPD Building Permit Policy 25-DCBC 507 (revised August 6, 2026) requires mechanical permits for kitchen hood exhaust systems to include sealed drawings from a single engineer covering hoods, duct, fans, makeup air, and controls, including the gas shutoff interlocked with the hood suppression system. On remodels, existing equipment must be shown with performance data.
- A new or modified hood suppression system needs its own Kitchen Hood Extinguishing System fire permit and a DFD acceptance test; the Fire Code lists a walk-through permit path for small hood extinguishing jobs (DFC §N103.9).
- See opening a new restaurant.
Grease interceptors: DOTI Wastewater
Interceptors are a sewer matter under DOTI Right-of-Way Services / Wastewater, not the fire code. Hood day still drains into them. See combining grease trap service with hood day.
- DOTI Policy 14.0 (effective January 5, 2026; authority DRMC §§56-102 and 56-104): grease interceptors required on all premises other than single-family or duplex homes where food is prepared or processed, or where an industrial process involves organic waste. Unless specifically permitted, only kitchen / food-processing waste may discharge to the interceptor — toilets and urinals do not.
- All kitchen, food-prep, food-processing, and dishwashing drains — including garbage disposals in those areas — must connect to the interceptor. Menu or process changes may require a previously permitted interceptor to be resized or redesigned; permits are required for new, modified, abandoned, reused, or reconstructed units.
- Pumping and cleaning is the owner’s or lessee’s responsibility; signed maintenance statements must be produced on request. General guideline: pump a gravity interceptor before FOG and solids reach 25% of liquid capacity; pump a hydromechanical unit per the manufacturer or before grease or solids reach 80% of storage capacity. Hydromechanical sizing for design commonly assumes a 1–3 month pumping cadence.
- Minimum accepted gravity interceptor: 750-gallon, two-compartment liquid capacity (any approved sizing method). Prefer exterior installation on private property; if DOTI allows an interior unit, it still cannot sit in a food-handling area under Environmental Health rules.
- The interceptor must be accessible for inspection; needing a ladder or moving bulky equipment to service it is an accessibility violation. SUDP grease-interceptor submittals (checklist effective August 17, 2026) need plumbing risers, fixture schedules, and sizing method documentation.
- Most locations with an existing interceptor have it inspected for condition and size before a Sewer Use and Drainage Permit is approved. Questions: wastewaterpermits@denvergov.org, 720-865-3060.
- Taking over an existing restaurant? See checking the exhaust system history. Ask your hood cleaner where wash water goes — interceptor only, not a storm drain or the lot. See chemical runoff and grease waste.
Food trucks
- Starting January 1, 2026, DFD uses the Fire Marshals Association of Colorado (FMAC) annual mobile food truck inspection. Propane trucks need an annual flammable operation permit, and the application includes a current six-month hood suppression inspection report with no deficiencies.
- The 2025 FMAC mobile checklist (based on the 2024 IFC) mirrors the fixed-kitchen picture: automatic extinguishing for the hood/duct (§904.2.2), suppression inspected and tested every six months and after activation by a licensed contractor (§904.14.5.2), Class K where solid fuels or vegetable/animal oils and fats are used (§906.4), and commercial cooking system inspection frequencies from Table 606.3.3.1 (including 3-month high-volume and 1-month solid-fuel rows). Keep the service tag and cleaning records where the inspector can see them.
- Food truck inspector: DFDMobiles@denvergov.org, 720-913-3405. See food truck hood cleaning.
Suburbs are a different AHJ
- Denver Fire Prevention, Denver Fire Code licensing (§116), and DOTI Policy 14.0 stop at the City and County of Denver line. A “Denver” mailing address in Aurora, Lakewood, Wheat Ridge, Centennial, or unincorporated Jefferson / Arapahoe County does not put you under DFD.
- West Metro Fire Rescue (Life Safety / Construction, 303-989-4307) publishes adopted codes by jurisdiction: City of Lakewood — 2021 IFC; City of Wheat Ridge — 2024 IFC; unincorporated Jefferson County — 2024 IFC; West Metro district board — 2024 IFC. Confirm whether the address is incorporated or unincorporated (Jeffco assessor / mill levy) before you book anyone.
- Aurora is its own AHJ: the Building Division handles life-safety plan review and inspections for Aurora Fire; Fire Prevention operational permits are at 303-326-8999. Aurora’s published fire-codes page (checked 2026-11-05) still lists the 2009 International Fire Code — confirm the current edition with the city before you copy Denver’s 2025/2024 schedule onto an Aurora kitchen.
- Parts of Centennial, Greenwood Village, Lone Tree, Parker, and unincorporated Arapahoe / Douglas County answer to South Metro Fire Rescue (9195 E Mineral Ave, Centennial; 720-989-2000). Ask which fire-code edition and report path that district uses for your address.
- When you request quotes, put the actual city or “unincorporated Jefferson / Arapahoe County” on the form so the cleaner brings the right AHJ paperwork.
Before you ask for quotes
- Which AHJ owns the address: City and County of Denver vs Aurora, Lakewood, Wheat Ridge, South Metro, or another district
- Your cooking tier from Table 606.3.3.1 (solid fuel = monthly; 24-hour / charbroil / wok = every 3 months; other = 6 months; low-volume worship / seasonal / senior = 12 months)
- Number of Type I hoods, duct length, and roof access (ladder, hatch, or lift) — see what drives quote variance
- Last hood inspection/clean tag and written report; last suppression service date (DFD-licensed Commercial Kitchen Hood/Extinguisher tech for Denver addresses; usually a different contractor from the grease cleaner)
- Class K extinguisher on the line with a current annual tag — DFD’s commercial-cooking checklist looks for it wherever grease is produced
- Interceptor type (gravity vs hydromechanical), size, last full pump-out date, and whether FOG/solids are under the 25% / 80% guidelines; whether hood wash water is routed to the interceptor
- Any open fire notice, and whether a first reinspection ($85) or subsequent reinspection ($165) is already on the calendar — separate from a $500 / $800 acceptance-test reinspection if you have permitted fire-system work open
- Outside Denver city/county, name the suburb or fire district on the quote request
Three separate jobs in a Denver kitchen
| Job | Rule we found | Proof |
|---|---|---|
| Hood, duct, and fan inspection and cleaning | DFC §606.3.3 / Table 606.3.3.1; IKECA C10 | Tag on the hood; written records kept |
| Hood suppression service | DFC §606.3.4 / §904.14.5; DFD license (§116) | Service tag and report from a DFD-licensed technician |
| Grease interceptor | DOTI Policy 14.0 (25% / 80% guideline) | Pumping records; signed maintenance statements on request |
Vet checklist
- Certs your AHJ accepts (IKECA or local equivalent): ask, then verify
- Certificate of insurance before they arrive
- Photo report: plenum, ducts, rooftop fan, not only the canopy
- Full-system vs canopy wipe in writing, with any inaccessible areas listed
- Tag on the hood with name, address, phone, and date
- If the same company services your suppression system (Denver addresses): a current DFD Commercial Kitchen Hood/Extinguisher license
- Wash water routed to the grease interceptor; no dump to a storm drain or the lot
- After-hours and roof access confirmed before the crew shows up
- Outside Denver: confirmation they know which fire district and code edition apply
Open listing slots
Sources
- Denver: 2025 Building and Fire Code adoption process (2024 I-codes adopted June 13, 2025)
- 2025 Denver Fire Code amendments (PDF) (§116 licenses; Chapter 6 amendments limited to §604)
- Denver Fire Code 2025, Chapter 6 (UpCodes) (§606.3.3, Table 606.3.3.1, records, tags, §606.3.4)
- DFD: Fire Safety Inspections (annual inspections; fee increase July 1, 2026; contacts)
- DFD Inspection Fee Schedule, July 23, 2026 (PDF) (reinspection $85 / $165)
- DFD: Plan review, construction, systems testing and occupancy (acceptance test reinspection fees; walk-through permits incl. DFC §N103.9)
- DFD: Mobile food vendors permitting process (FMAC inspections from 1/1/2026; suppression contractor license)
- DFD testing guide (PDF) (separate Kitchen Hood Extinguishing System permit; acceptance test items)
- CPD Building Permit Policy 25-DCBC 507: Kitchen hood exhaust system submittal requirements (PDF)
- Denver restaurant & commercial kitchen permits
- DOTI Policy 14.0: Requirements for grease interceptors, effective January 5, 2026 (PDF)
- DOTI: Sewer Use and Drainage Permits (existing interceptor inspections; contacts)
- Commercial plan review
- DFD Inspection Checklist (PDF) (Commercial Cooking block: 6-month suppression ITM, cleaning records, Class K)
- FMAC 2025 mobile food vendor inspection checklist (PDF) (§904.14.5.2 six-month suppression; Table 606.3.3.1; Class K)
- DOTI SUDP grease interceptor submittal checklist (PDF) (effective August 17, 2026)
- West Metro Fire Rescue: adopted fire codes by jurisdiction (Lakewood 2021 IFC; Wheat Ridge / unincorporated Jefferson County 2024 IFC)
- City of Aurora: Fire Codes (Building Division life-safety plan review; published 2009 IFC listing — confirm current edition)
- South Metro Fire Rescue: code compliance (Centennial / south-metro district contact)
Related guides
- How often to inspect
- Full-system vs canopy wipe
- What your report must show
- Suppression system vs hood cleaning
- Fire marshal reinspection fees
- Combining grease trap service with hood day
- Food truck hood cleaning
- Quote checklist
- What a full-system clean includes
- Phoenix · Austin · Kansas City
Request a listing: company, metro, certs, insurance, service area, photo-report policy. If you also service suppression systems in Denver, include your DFD license number.
Get quotes from local hood cleaners
Tell us about your kitchen and we'll pass the request to up to 3 local providers in Denver. No cost to you, no obligation.