Guide

Full-system hood clean vs canopy-only wipe

Updated 2026-09-16

The fire load lives in the path grease travels — filters, plenum, ducts, and the rooftop fan — not just the stainless you see from the cook line. A low quote that only shines the canopy leaves the risk in place.

Short answer Require the quote to name every section: hood, filters, plenum, horizontal duct, vertical duct, fan, grease containment. If ducts and fan are “extra,” you are buying a wipe, not a clean.
Canopy wipe versus hood-to-fan clean
Left: canopy wipe. Right: hood-to-fan clean.
Exhaust path diagram
Anything left dirty downstream of the canopy still carries grease.

Scope comparison

SectionFull-systemCanopy-only wipe
Hood canopyCleanedCleaned
FiltersRemoved / cleaned or replacedOften wiped in place
PlenumOpened and cleaned to metalUsually skipped
Horizontal ductAccessed via panelsSkipped
Vertical ductAccessed where panels existSkipped
Rooftop fanHinged / cleaned; grease cup checkedSkipped
PhotosEach sectionCanopy vanity shot

What good looks like

  • Written list of sections included
  • Inaccessible sections listed with reasons
  • Fan hinged and cleaned when design allows
  • Photo set matches the path diagram

What a cheap wipe looks like

  • “Hood cleaning” with no duct line item
  • Crew finished in far less time than roof access allows
  • No mention of fan or containment
  • Price far below other bids with no scope explanation

Field detail

Access that separates a full clean from a wipe

Secondary sources republishing NFPA 96 (2024 ed.) excerpts make the scope difference mechanical, not marketing: if the crew cannot reach a section, they cannot claim it was cleaned. Confirm section numbers against the edition your AHJ adopts.

Requirement (secondary NFPA 96 excerpt)Why a canopy-only bid fails it
§4.1.8 — all interior surfaces of the exhaust system shall be accessible for cleaning and inspectionA wipe that never opens the plenum or duct leaves interior surfaces untouched
§7.3.1 / §7.4.1.2 — openings at changes of direction; where a 20×20 in. entry is not possible, openings large enough for thorough cleaning at 12 ft (3.7 m) intervals on horizontal ductNo panel line-item usually means long horizontal runs stay greasy between elbows
§7.8.2.1(8) / §8.1.2.1 — hinged upblast fan with flexible weatherproof cable and service hold-open retainer for inspection/cleaningFixed fans or “roof not included” quotes skip the fan housing where grease collects
§8.1.2.3 — upblast fan drain to a readily accessible/visible grease receptacle not exceeding 1 gal (3.8 L)Canopy crews rarely check or empty rooftop containment
§12.6.1 — contaminated portions cleaned by properly trained, qualified, and certified person(s) acceptable to the AHJ (annex note cites ANSI/IKECA C10 as cleaning methodology guidance)“Hood cleaning” without duct/fan scope is not a full-system clean under that methodology framing

Operator move: put duct access, fan hinge, and grease-cup checks on the same bid sheet as the canopy. If the vendor marks sections inaccessible, get that in writing and schedule panel work — do not accept a shiny canopy as proof the path is clean. See duct access panels, rooftop fan access, and grease cup / rooftop containment.

Who it’s for / not for

Sources