What a reinspection notice for exhaust cleaning usually cites

Updated 2026-10-10

A fire inspector walks the line, looks up into the hood, checks the tag, and asks for the last cleaning report. If something is off, you get a notice with a correction date and a reinspection. Most of those notices cite the same short list of items, and most of them are paperwork or access problems you can close before the inspector comes back.

Short answer Expect citations for: inspection or cleaning overdue for your cooking type, visible grease in the hood, plenum, duct, or fan, no written report on site, a missing or outdated service tag, filters missing or gapped, inaccessible duct sections, and suppression service overdue. Read each line of the notice, decide whether it belongs to your hood cleaner, your suppression contractor, or your own staff, and bring proof to the reinspection: dated report, photos, and the new tag. Missed reinspections and open items can carry a fee.

The usual citations and who fixes them

What the notice says (in substance)Code hook inspectors useWho closes it
Exhaust system not inspected or cleaned at the required intervalIFC Table 606.3.3.1 (Table 609.3.3.1 in older editions): 1, 3, 6, or 12 months by cooking typeHood cleaner; you book it
Grease accumulation in hood, plenum, duct, or fanIFC 606.3.3.2: clean to ANSI/IKECA C10; NFPA 96 “clean to bare metal” language on many AHJ checklistsHood cleaner
No cleaning report or certificate on the premisesIFC 606.3.3.3 records: who inspected or cleaned, which company, whenYou (file it); cleaner (send it)
No service tag, or old tags still on the hoodIFC 606.3.3.3.1: tag with provider name, address, phone, date; prior tags covered or removedHood cleaner
Filters missing, damaged, or with gapsIFC 606.3.1: listed grease filters in place when cooking under the hoodYour staff, same day
Duct sections not accessible or not cleanedAccess panel and cleanout rules in the mechanical code and NFPA 96; report must list areas not cleanedCleaner documents it; landlord or HVAC contractor adds panels
Suppression service tag older than six months, or more than one tagSuppression service is a separate section (IFC 904; NFPA 17A); some states add tag rulesSuppression contractor, not the hood cleaner
Nozzle caps missing, fusible links not replaced, pull station blockedNFPA 17A / NFPA 96, as listed on AHJ checklistsSuppression contractor; staff keep the pull station clear

Section numbers move between editions. Your notice should cite the code your city adopted. If it doesn’t, ask the inspector which section and edition before you pay anyone to “fix” it. See inspection vs cleaning and suppression vs hood cleaning.

What real AHJ checklists look at

Two public examples show what inspectors and cleaners are told to check:

If your cleaner’s report doesn’t cover those points, it won’t help much at a reinspection. See what your report must show.

Before the reinspection

Reinspection fees

Many cities charge for return visits. One published example: the Phoenix Fire Prevention Fee Schedule (effective 1/20/2026) lists a reinspection fee of minimum $195 (1 hour) when corrections aren’t made, cited items are still open at reinspection, access isn’t provided at the scheduled time, or more inspections are needed. Your city’s amount is Unknown until you check its fee schedule; see how to research reinspection fees.