Opening a new restaurant: first hood cleaning and inspection timing

Updated 2026-10-10

A new kitchen meets the hood rules twice: once during construction, when the duct, hood, and suppression system have to pass tests before the fire marshal signs off, and again after opening, when the inspection clock for your cooking type starts running. Owners tend to plan the first and forget the second until the first fire inspection asks for a cleaning report.

Short answer Before opening: the grease duct gets a leak test before it’s covered up, the hood gets a performance test, and the suppression system gets an acceptance test witnessed or reviewed by the fire department, all before final approval and your certificate of occupancy. After opening: count from your first day of cooking and book the first exhaust inspection at the interval for your cooking type: 1 month for solid fuel, 3 months for high-volume, 6 months for most kitchens, 12 months for low-volume. Sign the cleaning vendor before opening; some AHJs ask for the maintenance agreement at final inspection.

During construction: the tests that gate your opening

StepWhat it isWho handles it
Grease duct leak testBefore any part of the grease duct is used or concealed (in a shaft or under wrap), a light test (lamp of at least 1,600 lumens passed through the duct, no light visible outside) or a 1,200 psi water spray test, covering the whole system including the hood-to-duct joint (2024 IMC §506.3.2.5)Mechanical contractor (permit holder); inspector per local practice
Hood performance testExhaust and makeup airflow and proper operation verified before final approval, plus a capture and containment check with appliances hot and smoke or steam visible (2024 IMC §507.1.7)Mechanical contractor; air balance firm if required
Suppression acceptance testStatement of compliance, NFPA 17A record of completion, piping flow (balloon or puff) test, manual pull test, detector or fusible link test, automatic fuel and power shutoff, alarm tie-in where requiredSuppression contractor, with the fire inspector
Fire final and certificate of occupancyFire inspection of the space, including the hood system, before COGeneral contractor schedules; owner attends

Local paperwork varies. The Oklahoma State Fire Marshal publishes a hood suppression final inspection list that includes the items above. Seattle Fire requires the suppression acceptance form in The Compliance Engine before the hood suppression sign-off. Monroe County Fire Rescue (Florida) asks to see an air balance report and a copy of the cooking equipment maintenance agreement, and warns that unfinished items can mean a re-inspection fee.

Things the cleaner should see before you open

A short pre-opening walk with the cleaning company you plan to use is not a code requirement. It is a cheap way to find inaccessible sections while the contractor is still on the job.

After opening: when the first inspection is due

Cooking type (IFC Table 606.3.3.1)First inspection, counting from first day of cooking
Solid fuel (wood, charcoal)1 month
High-volume: 24-hour, charbroiling, wok3 months
All other cooking6 months
Low-volume: places of worship, seasonal, senior centers12 months

The code doesn’t say when the clock starts for a new system; counting from the first day of cooking is our working rule, and your AHJ can set its own. If the inspection finds grease, the system gets cleaned to ANSI/IKECA C10, and you keep the record and tag (§606.3.3.2 through §606.3.3.3.1). New kitchens with unknown volume often run hotter than the owner planned, so look up into the hood and at the filters monthly for the first quarter (inspection frequency).

Opening-week checklist

Who it’s for / not for

Sources