Guide
How often to inspect a commercial kitchen exhaust system
Your cook line makes grease. The question is how often someone qualified looks at the whole exhaust path — and when that look turns into a clean. Operators who only “clean when it looks dirty under the canopy” get surprised on duct and fan inspections.
Inspection interval by cooking type
Secondary industry sources cite NFPA 96 Table 12.4 (2024 ed.) as an inspection schedule. Confirm against the edition your city adopts.
| Cooking type | Typical examples | Inspect |
|---|---|---|
| Solid-fuel | BBQ, wood-fire pizza, charcoal | Monthly |
| High-volume | 24-hour kitchens, charbroil, wok lines | Quarterly |
| Moderate-volume | Most sit-down restaurants | Semiannually |
| Low-volume | Churches, day camps, seasonal, senior centers | Annually |
What good looks like
- Calendar matches your heaviest cooking type on site
- Inspection covers hood → filters → plenum → ducts → fan
- Written finding if cleaning is due; photos if cleaned
- Next-due date on the hood service label
What a cheap wipe looks like
- “We clean every 6 months” with no cooking-type logic
- Only filters or canopy wiped; ducts/fan never opened
- No measurement notes; no inaccessible-area callouts
- Sticker date with nothing behind it
Field detail to check tonight
- Hood sticker / service label — last service date and company name visible?
- Access panels — enough panels to reach horizontal and vertical duct, or “couldn’t access” forever?
- Rooftop fan — hinged for cleaning? Grease cup / containment present?
- Before/after photos — plenum, duct opening, fan interior — not just a shiny canopy
- Next-due date — on the report and on your wall calendar
Inspection vs cleaning (what the schedule actually is)
Secondary sources summarizing NFPA 96 (2024 ed.) treat Table 12.4 as an inspection cadence, not a fixed “clean every X months” calendar. Cleaning is triggered when grease depth crosses the limits your AHJ applies. Confirm section numbers and limits against the edition your city adopts — do not treat this page as the code book.
| Where grease is measured | Depth often cited as the clean trigger (secondary) |
|---|---|
| Hoods, filters / grease removal devices, fans, ducts | ~0.002 in (≈50 µm — about copy-paper thickness) |
| Other surfaces inside the system | ~0.078 in (≈2 mm) |
| Fan housings | ~0.125 in (⅛ in) |
Practical operator read: solid-fuel and high-volume lines usually need a real clean on the same visit as the inspection. Moderate- and low-volume kitchens may pass an inspection without a full clean that cycle — but they still need the written report and a current service label. Related maintenance cadences secondary sources also flag: wet-chemical suppression service on its own schedule (often semiannual), and grease drip containers checked/emptied on a short staff cadence (often weekly).
Where your city changes the schedule (checked 2026-10-21)
Most cities we cover adopt the same four-row table, either as International Fire Code Table 606.3.3.1 (607.3.3.1 in older editions) or NFPA 96 Table 12.4. The rows match the table above. What changes from city to city is who must do the work, whether the report gets filed with the fire department, and in a few places the interval itself.
| City | Interval source | What's different |
|---|---|---|
| New York | 2022 NYC Fire Code FC 609 (its own tables) | Inspect and clean every 3 months by an FDNY-approved company, regardless of volume; ducts more than 3 floors above the kitchen go to 6 months except high-volume |
| Boston | 527 CMR 1.00 Ch. 50 (Table 50.5.4) | Standard four rows; state-licensed inspector and cleaner, Boston Fire registration, and a cease and desist where no inspection in the past 12 months |
| Phoenix | 2024 IFC Table 606.3.3.1 | Cleaner files every report with Phoenix Fire through The Compliance Engine within 30 days, pass or fail |
| Nashville | 2024 IFC Table 606.3.3.1 | Hood cleaning reports go through Inspection Reports Online |
| Miami | NFPA 96 (2021) Table 12.4 | City of Miami and Miami-Dade Fire Rescue enforce separately, so check which one covers your address |
| San Antonio | 2024 IFC Table 606.3.3.1 | Standard four rows; the fire code official may approve a different interval; tag with provider name, address, phone, and date |
Two practical reads. First, if you run a kitchen in New York, the cooking-type table on this page is not your schedule; FDNY's 3-month clean is. Second, "inspect" and "file" are different deadlines in Phoenix and Nashville: a clean that happened but never reached the fire department's portal can still show up as missing. Open your city page for the source text before you set the calendar.
Volume-specific planners on this site
Use the table above to pick your tier, then open the matching planner:
- Solid-fuel (wood/charcoal) — monthly reality check
- High-volume fryer line — quarterly planner
- Moderate-volume restaurant — semiannual checklist
- Low-volume / church kitchen — annual minimums
Who it’s for / not for
- For: kitchen managers, multi-unit facilities, owners planning vendor cadence
- Not for: treating this table as a legal determination — your AHJ and adopted code edition control
Sources
- Facilitec Southwest — NFPA 96 frequency / inspection-vs-cleaning guide (secondary; depth table + Table 12.4 summary)
- Facilitec — NFPA 96 codes reference (secondary)
- Total Fire Protection — frequency summary (secondary)
- IKECA FAQs
- 2022 NYC Fire Code Chapter 6, FC 609 (PDF)
- Mass.gov DFS: Commercial cooking exhaust system inspections
- Phoenix Fire Prevention: 2026 Explanatory Policy Manual (PDF)
- Nashville Fire: Inspection Reports Online
- San Antonio Fire Code 2024 Chapter 6 (UpCodes)
Next step
Open your last invoice or sticker. If the date doesn’t match the cooking-type row above, schedule an inspection — not a canopy wipe — and require duct and fan photos.
Get quotes from local hood cleaners
Tell us about your kitchen and we'll pass the request to up to 3 local providers in your area. No cost to you, no obligation.