Wood-fire pizza, charcoal grills, smokers, and pellet cookers put creosote and ash into the exhaust path on top of grease. Operators who keep a “quarterly hood clean” contract after adding solid fuel are usually on the wrong row of the inspection table — and creosote doesn’t wait for the calendar.

Short answer Secondary industry sources citing NFPA 96 Table 12.4 (2024 ed.) put systems serving solid-fuel cooking on a monthly inspection floor. Cleaning is triggered when grease/creosote depth crosses the limits your AHJ applies — in solid-fuel kitchens that usually means you should budget a full-system clean on most monthly visits, not a canopy wipe every three months. Confirm the edition your city adopts.

What changes with solid fuel

FactorGas / electric lineSolid-fuel line
Inspection cadence (Table 12.4, secondary cite)Quarterly / semi / annual by volumeMonthly
Deposit typeMostly grease filmGrease + creosote + ash / soot
Ignition extrasGrease fire riskEmbers / sparks into ducts if spark arrestors missing or gapped
Filter realityBaffle filters; staff clean on a set cadenceListed spark-arrestor filters; often daily or multi-times-per-week staff cleaning
Cheap-wipe failure modeShiny canopy, dirty duct/fanSame — plus creosote left in vertical runs and fan housing

What a solid-fuel visit should cover

  • Hood canopy, listed spark-arrestor filters (flush, no bypass gaps)
  • Plenum, horizontal and vertical duct, access panels opened
  • Rooftop fan interior + grease cup / containment
  • Written note if any section stayed inaccessible
  • Before/after photos of plenum, duct opening, fan — not only the canopy

Patterns that fail solid-fuel kitchens

  • Keeping a quarterly contract after adding a wood oven or charcoal grill
  • Standard baffle filters where spark arrestors are required
  • “Couldn’t access” forever on vertical duct with no panel plan
  • Staff never washing spark arrestors between professional visits
  • Report with no creosote callout and no duct/fan photos

Field checklist this month

Inspection vs cleaning (don’t blur the words)

Table 12.4 is an inspection schedule. Cleaning is required when measured deposits exceed the depth limits secondary sources attribute to NFPA 96 Section 12.6.1.1 (commonly cited: ~0.002 in on hoods/filters/fans/ducts). In solid-fuel kitchens, creosote plus grease usually crosses that line between monthly visits — so plan the budget as monthly full-system work unless your written inspection report says the system stayed under threshold.

Spark arrestors and Chapter 15 filter rules (secondary)

Monthly inspection is only half the solid-fuel problem. Secondary republishers of NFPA 96 (2024 ed.) Chapter 15 add equipment rules for grease-removal devices when wood, charcoal, or other solid fuel can throw sparks and embers into the exhaust path. Confirm the edition and section numbers your AHJ adopts before you rewrite a filter order.

Requirement (secondary NFPA 96 excerpt)Operator check on the line
§15.5.1 — grease removal devices constructed of steel or stainless steel, or otherwise approved for solid-fuel cookingDo not stock lightweight / unlisted baffles on a solid-fuel hood; match listing to the appliance risk (see hood filters: clean vs replace)
§15.5.2 — where airborne sparks and embers can be generated, spark arrester devices shall be used prior to the grease removal device so sparks/embers do not enter the grease filter, hood, and ductConfirm listed spark-arrestor arrangement (often diamond-pattern face) seated flush with no bypass gaps; staff wash cadence is usually daily or multi-times per week
§15.5.3 — filters a minimum of 4 ft (1.2 m) above the appliance cooking surfaceFlag low-mounted banks when a wood oven or charcoal grill was added under an existing hood — that is an equipment/layout issue, not a wipe-day fix
Table 12.4 + Chapter 15 — solid-fuel systems on a monthly inspection floor; creosote + ash load vertical runs and fan housings fastBudget full-path cleaning on most monthly visits; demand duct/fan photos and creosote callouts on the report (see grease depth thresholds and vertical duct sections that get skipped)

Industry solid-fuel write-ups (Kitchen Guard and others) stress the same field pattern: missing or wrong spark arrestors, creosote left in vertical duct, and quarterly contracts after a wood oven was added. For concept-specific calendars, see BBQ / smokehouse creosote + grease notes and wood-fired pizza oven hood schedule. “Clean” still means the path was opened — not a canopy shine (see what bare metal clean means).