Directory · Miami
Miami commercial kitchen hood cleaning
Research index for operators. Public rules we found, how to vet a cleaner, open listing slots. Not a ranked vendor list.
First, which fire marshal is yours
- Inside City of Miami limits: the City of Miami Fire-Rescue Fire Prevention Bureau handles Certificate of Use / Fire Safety Permit inspections, plans review, and annual life safety inspections in all existing businesses. Contact: 305-416-1600, FirePrevention@miamigov.com.
- Unincorporated Miami-Dade and cities served by Miami-Dade Fire Rescue (MDFR): every business needs an annual inspection and a Life Safety Operating Permit. The inspector records violations, returns in 30 days to re-inspect, and mails the annual permit once corrected. Uncorrected violations get a Final Notice of Violation and go to Code Compliance.
- Miami Beach, Coral Gables, Hialeah, and other cities with their own fire departments are their own AHJ. A “Miami” mailing address does not settle it. Check your last fire inspection report or Certificate of Use.
What code applies
- Florida writes one statewide fire code: the 8th Edition Florida Fire Prevention Code (NFPA 1 and NFPA 101, 2021 editions, with Florida amendments). Miami-Dade has local amendments filed with the State Fire Marshal (linked below).
- Commercial kitchen exhaust is governed by NFPA 96 (2021), which Florida adopts without amendments. The 9th Edition rulemaking proposes moving to NFPA 96 (2024) with a proposed effective date of December 31, 2026. Ask your inspector which edition they cite after that date. The Orlando page has the detail on that change: Orlando.
- Hood installation is a building matter: Miami-Dade’s permit categories list mechanical category 38 COMMERCIAL HOODS, and fire plan review may involve MDFR. The county mechanical fee sheet lists commercial hoods at $206.49 per hood on a separate application (unincorporated county; cities with their own building departments set their own fees).
Inspection intervals (NFPA 96 Table 12.4)
We found no Miami-only interval calendar. The statewide NFPA 96 table is what applies:
| Type or volume of cooking | Inspect for grease buildup |
|---|---|
| Solid fuel cooking | Monthly |
| High-volume: 24-hour cooking, charbroiling, wok | Quarterly |
| Moderate-volume (most restaurants) | Semiannually |
| Low-volume: churches, day camps, seasonal businesses, senior centers | Annually |
- If inspection finds grease-laden deposits, cleaning is done by a properly trained, qualified, and certified person acceptable to the AHJ. Under the 2021 edition a certificate showing the company, the person, and the date stays on the premises.
- Seasonal kitchens on the beach or in hotels that close part of the year: see seasonal kitchens before reopening.
Fees we found (Miami-Dade Fire Rescue)
MDFR Implementing Order 04-123, effective October 1, 2025, sets annual operating permit fees by occupancy. Restaurants with 50 or more occupants fall under assembly; confirm your category on your last MDFR invoice.
| Item | Fee (IO 04-123) |
|---|---|
| Assembly occupancy annual permit, up to 49 persons | $92.23 |
| Assembly, 50–99 persons | $133.37 |
| Assembly, 100–300 persons | $175.74 |
| Assembly, 301–1,000 persons | $221.86 |
| Flammable/combustible/hazardous materials or processes, “including outdoor cooking” | Additional 50% of the permit fee, or $140.83 for non-permit occupancies |
| Life Safety Permit re-inspection (more than one re-inspection) | Half the original permit fee, maximum $316.57 per re-inspection |
Unknown on this page: City of Miami Fire Prevention Bureau’s current annual inspection fee for restaurants. We could not confirm it from the city’s published fee pages. Confirm with FPB at 305-416-1600. See how to research reinspection fees.
Suppression: Florida licensing
- Hood suppression service is every six months and is a separate job from grease cleaning. Florida licenses that work through the State Fire Marshal: a Class D fire equipment dealer license covers pre-engineered systems such as wet chemical hood systems (Fla. Stat. §633.304).
- We found no Florida state license class for hood and duct cleaning. Ask for certifications your AHJ accepts.
- After cleaning day, check nozzle caps and appliance positions before cooking. See nozzle caps and coverage.
Grease traps: Miami-Dade FOG permit
- Any non-residential facility that prepares food and can discharge fats, oils, or grease to the public sewer needs a Miami-Dade FOG Discharge Control Operating Permit, issued by the county’s environmental resources program (DERM). It is renewed annually and non-transferable; a new owner needs a new permit. Inside a city, you apply for the municipal license or Certificate of Use first.
- Pump-outs are done by a liquid waste transporter permitted by the county. You report each pump-out online by the 20th of each month: your GDO permit number, the hauler’s LW permit number, the date, and the company (county FSE reporting guide, April 2026).
- The cleaning frequency is written into your permit. The county’s FOG Control Program document (2017) describes every 30 days for hydromechanical interceptors and every 60 days for gravity interceptors, with alternative frequencies up to 90 days only by approval. Check the frequency printed on your own permit.
- Self-cleaning is allowed only for small interceptors (20 gpm or less) at places with no fryers that are not required to have a Type I hood, with daily cleaning and logs kept three years. If you have a grease hood, plan on a permitted hauler.
- Hood wash water goes to the interceptor, not a storm drain. See chemical runoff and grease waste.
Miami Beach, Coral Gables and Broward: what changes outside MDFR
If your kitchen sits in a city with its own fire department, or across the county line in Broward, the paperwork after cleaning day is different. What we found on each office’s own documents:
| Where | What the fire office looks for | What it means for your quote |
|---|---|---|
| Miami Beach | Annual fire safety permit, renewed by invoice to Certificate of Use holders. FY 2025 schedule: assembly Class C (50–300 persons) $80, Class B (301–1,000) $117, Class A (over 1,000) $156. Rates are adjusted each year by CPI. The fire prevention office posts a semi-annual cooking equipment extinguishing system checklist. | Installing or altering a hood suppression system is a fire permit: $328 per system in FY 2025, additional systems in the same kitchen at 50%. After-hours (“enhanced”) fire inspections run $150 per hour plus a $75 travel minimum, requested 24 hours ahead. |
| Coral Gables | The fire department’s pre-inspection checklist (item 10): all commercial cooking equipment protected by a suppression hood system that is clean of grease, including filters, fusible links replaced, and a current certification tag. Paperwork for all fire protection systems kept on site. | Inspectors look at the hood and filters directly. Book cleaning before your fire inspection, not after. We could not confirm the city’s current annual restaurant fire inspection fee (Unknown). |
| Broward County (all cities, incorporated and unincorporated) | County amendments to the Florida Fire Prevention Code, F-123: the cleaner must meet IKECA training (or another national association the fire office accepts); proof of training goes to the local fire office before cleaning starts; the NFPA 96 cleaning report goes to the owner, and a copy with before and after photos goes to the local fire office. F-122.2.1 also calls for the floor under and the wall behind appliances to be cleaned of grease. | Ask any Broward vendor whether their certification is already on file with your city’s fire office and whether they submit the photo report for you. A vendor who doesn’t take photos isn’t meeting the county rule. |
| Fort Lauderdale | Fire Rescue’s Fire Prevention Bureau runs annual inspections after the CO; the inspection fee schedule is set by city ordinance. An Oakland Park Fire Rescue agenda item lists Fort Lauderdale as already using The Compliance Engine, the online system where service companies file inspection and cleaning reports. | Ask whether the vendor files your report through The Compliance Engine and who pays the filing fee. Fire Prevention Bureau: 954-828-6370, fireprevention@fortlauderdale.gov. |
Quote prep for these cities: have your last cleaning report, your suppression tag date, and your fire safety permit or Certificate of Use number ready. In Broward, add the name of the fire office that inspects you, since the vendor’s certification and photo report go there.
Three separate jobs in a Miami kitchen
| Job | Rule we found | Proof |
|---|---|---|
| Hood, duct, and fan inspection and cleaning | FFPC / NFPA 96 (2021) Table 12.4; annual fire inspection by City FPB or MDFR | Certificate on premises; label on the hood |
| Hood suppression service | Every six months; Class D dealer (Fla. Stat. §633.304) | Service tag less than six months old |
| Grease trap / interceptor | Miami-Dade FOG Discharge Control Operating Permit; frequency on permit; monthly online pump-out report | Permit posted; hauler manifests; monthly report |
Vet checklist
- Certs your AHJ accepts (IKECA or local equivalent): ask, then verify
- Certificate of insurance before they arrive
- Photo report: plenum, ducts, rooftop fan, not only the canopy
- Full-system vs canopy wipe in writing, inaccessible areas listed
- Certificate and label left on site with company, technician, and date
- If the same company services suppression: a Florida Class D license number
- After-hours and roof access confirmed before the crew shows up; wash water routed to the interceptor
Open listing slots
We do not invent vendors. Listing here requires docs sent through our contact form.
Sources
- City of Miami — Fire Prevention Bureau (CU / Fire Safety Permit inspections; annual life safety inspections of existing businesses; 305-416-1600)
- Miami-Dade County — Life Safety Operating Permit (annual inspection for all businesses in MDFR jurisdiction; 30-day re-inspection; Final Notice of Violation)
- Miami-Dade Fire Prevention Fee Schedule, Implementing Order 04-123, effective 10/01/2025 (PDF) (assembly permit fees; process add-on incl. outdoor cooking; re-inspection max $316.57)
- Florida Fire Prevention Code (8th edition; 9th edition rulemaking)
- Florida Commercial Cooking Ventilation and Fire Protection Code 2021 (UpCodes) (adopts NFPA 96-2021)
- Hood Cleaning School: NFPA 96 excerpts (secondary; Table 12.4 text)
- Miami-Dade local amendments (PDF)
- Miami-Dade municipal permit categories (PDF)
- Miami-Dade mechanical fee sheet (PDF) (Category 38 commercial hoods, $206.49 per hood)
- Miami-Dade life-safety pre-submittal checklist (PDF) (cooking appliances ventilation/suppression per NFPA 101)
- Miami-Dade mechanical inspection guidelines (PDF)
- Florida Statutes §633.304 (2026) (Class D license; preengineered permit)
- Miami-Dade — FOG Discharge Control Operating Permit (annual, non-transferable; municipal license/CU first)
- Miami-Dade — FSE guide to electronic pump-out reporting, April 2026 (PDF) (report by the 20th of each month; self-cleaning conditions: no fryers, no Type I hood required)
- Miami-Dade FOG Control Program and Ordinance, Oct. 2017 (PDF) (30-day hydromechanical / 60-day gravity cleaning; alternatives up to 90 days by approval)
- City of Miami Beach FY 2025 Fee Schedule (PDF) (§50-10(a) cooking hood suppression $328/system, 50% each additional; §50-12 assembly fire safety permit $80/$117/$156)
- Miami Beach Code ch. 50 (annual fire safety permit; CPI adjustment)
- Miami Beach Fire Prevention — existing building inspections (semi-annual cooking equipment extinguishing systems checklist)
- Miami Beach enhanced (overtime) inspections ($150/hr, $75 travel minimum, 24-hour notice)
- Coral Gables Fire Department fire/life safety inspection checklist (PDF) (item 10: hood clean of grease incl. filters, fusible links, current tag)
- Broward County Local Amendments to the Florida Fire Prevention Code, 2025 (PDF) (F-122.2.1; F-123.2–F-123.4 training certification before cleaning, report with before/after photos to local AHJ)
- Fort Lauderdale Fire Prevention Bureau (annual inspections; fee schedule by ordinance; contact)
- Oakland Park agenda item on The Compliance Engine (lists Fort Lauderdale as an existing user)
Related guides
- How often to inspect
- Full-system vs canopy wipe
- What your report must show
- Nozzle caps and coverage after cleaning
- Quote checklist
- What a full-system clean includes
- Orlando (incl. Seminole and Kissimmee) · Tampa (incl. St. Petersburg and Pinellas) (same Florida Fire Prevention Code; city vs county AHJ split)
Request a listing: company, metro, certs, insurance, service area, photo-report policy.
Get quotes from local hood cleaners
Tell us about your kitchen and we'll pass the request to up to 3 local providers in Miami. No cost to you, no obligation.