Grease depth thresholds explained (secondary-sourced; verify NFPA)

Updated 2026-09-15

Inspection cadence and cleaning trigger are different jobs. Secondary NFPA 96 explainers say Table 12.4 sets how often someone measures grease; Section 12.6.1.1 sets how much grease forces a clean. Operators often hear “one-eighth inch” as a universal rule — secondary sources say that number is the fan-housing threshold, not the whole system. Numbers below are secondary summaries. Buy or cite the edition your AHJ adopted; this is not the official text and not legal advice.

Short answer Secondary 2024-edition explainers describe three measured limits checked with a grease depth-gauge comb: about 0.002 in (50 μm) on hoods / grease-removal devices / fans / ducts (often framed as the tight limit or clean-to target), about 0.078 in (2000 μm) on other surfaces as a cleaning-required depth, and about 0.125 in (3175 μm) inside fan housings. Crossing the applicable limit triggers cleaning under the secondary §12.6 framing. Your AHJ’s adopted edition and local amendments win — verify before you argue with a marshal.

Secondary threshold table

Where (secondary framing)Depth (secondary)Rough feelCited section (secondary)
Hoods, grease-removal devices (filters), fans, ducts0.002 in / 50 μm~ copy-paper thickness§12.6.1.1.1
Other surfaces (non–fan-housing)0.078 in / 2000 μm~ US nickel thickness (secondary analogy)§12.6.1.1.3
Fan housings0.125 in / 3175 μm1/8 in (~ two dimes stacked, secondary analogy)§12.6.1.1.4

Micron note: secondary sources use 3175 μm for 0.125 in — not the informal “3250” sometimes seen in shorthand. Always prefer the inch figure plus your edition’s text.

How the measurement works (secondary)

Field note — framing variance to watch

Operator use that holds up

  • Ask the inspector where they measured and which threshold they applied
  • Require the written report to list inaccessible areas instead of silent skips
  • Budget cleaning at every inspection for solid-fuel / high-volume (secondary operational reality)
  • Keep the depth reading (or photo of the comb) with the visit file when provided

Common misunderstandings

  • “We’re under 1/8 inch on the canopy — we’re fine” (wrong surface / wrong number)
  • Eyeballing grease instead of a gauge
  • Confusing inspection sticker cadence with automatic cleaning
  • Treating a secondary blog table as the legal text

How this ties to scheduling

Cooking tier (secondary Table 12.4)InspectPractical cleaning plan (secondary)
Solid fuelMonthlyPlan a clean nearly every cycle — creosote + grease load fast
High volume (24-hour, charbroil, wok)QuarterlyUsually clean at the same visit — 0.002 in is easy to cross
Moderate volumeSemiannualInspect on schedule; clean when depths trip
Low volume (church, seasonal, senior)AnnualMay pass without a clean some years — still need the written report