Directory · Houston

Houston commercial kitchen hood cleaning

Research index for operators. Public rules we found, how to vet a cleaner, open listing slots. Not a ranked vendor list.

HFD Life Safety Bureau · Houston Fire Code 2021 (IFC-based) · Table 606.3.3.1 · ANSI/IKECA C10 · FOG ≠ exhaust · Updated 2026-11-17

What operators usually get asked

Inspection intervals (Table 606.3.3.1, Houston Fire Code 2021)

Type of cooking operationInspect at least every
Solid-fuel cooking (wood, charcoal)1 month
High-volume: 24-hour cooking, charbroiling, wok3 months
All other cooking6 months
Low-volume: places of worship, seasonal businesses, senior centers12 months

The fire code official can approve a different interval. The table sets how often someone qualified looks at the system. Cleaning happens when that inspection finds grease. See inspection vs cleaning.

Three separate jobs in a Houston kitchen

JobRule we foundWho files or keeps proof
Hood, duct, and fan cleaningHouston Fire Code §606.3.3 + Table 606.3.3.1; clean to IKECA C10; LSB Standard 02 “as often as necessary”Cleaner leaves a tag and a record. Keep both on site.
Hood suppression inspectionLSB Standard 02 §2.9.1: inspect and tag at least every 6 months; UL 300; Texas FEL-K contractorLicensed suppression company. Different trade from grease cleaning.
Grease trap / FOG pump-outHouston Code Ch. 47: interceptors fully evacuated at least every 90 days unless a waiver is approved; FOG generator permitCity-permitted hauler; keep manifests on site (city says five years). Health Department program — not HFD exhaust cleaning.

Houston Health’s food-establishment BMP sheet also tells operators to clean hood filters regularly and to put hood/filter waste into a mop sink or fixture that drains to a grease trap — or have the hood professionally maintained. Surfactants and emulsifiers meant to push grease through the trap are prohibited. A hood cleaner’s wash water is a separate question; ask where it goes. See chemical runoff and grease waste.

What the City of Houston charges (2026 schedule)

These are City of Houston numbers from the Permitting Center and the city-wide fee schedule, both dated January 2026. Inside city limits, the hood suppression permit goes through Building Code Enforcement; the annual assembly permit and re-inspections come from the Fire Marshal’s Office.

ItemFeeWhen it applies
Type 1 hood fire suppression system permit (Form CE-1047)$97.56 minimum per system, plus a $33.56 administrative feeNew or replaced hood suppression system. No separate plan review is required for a standalone Type 1 hood system.
Place of assembly permit, 50–100 occupants$268.56Dining rooms and bars at that load (Fire Code §105.6.34; includes part of the life safety inspection)
Place of assembly permit, 101–299 occupants$402.84Same permit, larger room
Place of assembly permit, 300+ occupants$537.12Same permit, largest tier
Re-inspection, other than fire protection systems$402.84Fire Code §113.1.3.1. The schedule lists this for re-inspections not tied to fire protection system or fuel tank permits.
Open flames and candles permit$167.84Table candles, flambé, or other open flame in an assembly space (§105.6.32)

We did not find a published city fee for filing a hood cleaning report. If a Fire Marshal inspection turns up a dirty hood, the cheapest outcome is a cleaning report and service label dated before the inspector comes back. To get a copy of a past Fire Marshal inspection record for your address, the office takes open records requests (see its FAQ page under Sources).

Before you call for a quote

Outside city limits: unincorporated Harris County

A kitchen in unincorporated Harris County (outside Houston and the other incorporated cities) answers to the Harris County Fire Marshal’s Office, not HFD. The county adopts the 2021 International Fire Code, so the same Table 606.3.3.1 intervals apply. The paperwork and fees are different:

Before you call for quotes, confirm which office has your address. A Houston mailing address does not mean the City of Houston is your fire code official.

Sugar Land, Pasadena, Pearland and Fort Bend County

The suburbs each run their own fire marshal’s office, with their own fees and their own rules on where hood paperwork goes. What each office publishes:

Fire code officialWhat applies to a commercial kitchenHood report filing
City of Sugar Land Fire Marshal’s Office (2024 ICC codes from Jan 21, 2026)Kitchen extinguishing system permit $330.50, first inspection included; each failed or not-ready re-inspection $123.50. Annual operational permit $125.25 single, $322.50 for one to three items. Fees double if work starts before the permit. Rates per Ordinance 2382, effective Jan 1, 2026. Permits go through the city’s Citizen Self Service portal only; a suppression permit that is part of a build-out must be added under the general contractor’s building permit, or it is rejected.Since Oct 15, 2021, contractors must submit every report, passing or failing, through Brycer’s The Compliance Engine. The city’s tracked-system list includes commercial kitchen exhaust cleaning, semi-annual and hood suppression, semi-annual.
City of Pasadena Fire Marshal’s Office, 713-475-5556 (2024 IFC with local amendments)Annual Fire and Life Safety Operating Permit for assembly occupancies (restaurants, bars, banquet halls): $250 for 1–99 occupants, $350 for 99–299 (tiers as the city prints them), $500 for 300+. Automatic extinguishing system plan review $200. Re-inspection $150 after the first inspection and first re-inspection. After-hours inspection $375 for the first 3 hours, $70 per added hour. Suppression plans need the installer’s state license and a certificate of insurance.We found no published hood report filing rule. Keep the cleaning report and service label on site.
City of Pearland Fire Marshal’s Office, 281-997-4650Fire Marshal fees: commercial cooking inspection $150, IFC operational permit $150, re-inspection $75 (Ordinance 1358-33, June 2026; same amounts as FY26). Permits, inspections, plan review and payments run through the city’s Cityworks portal (since January 2025). Plan review for fire extinguishing systems is half the permit fee, about 10 business days. A system installed before plan approval will not be inspected and gets double fees.No published hood report filing rule found. Ask the inspector what they want to see.
Fort Bend County Fire Marshal’s Office (unincorporated areas it covers), 281-238-1500Fee amounts were not checked for this page.Since Aug 1, 2025, service providers must file every fire protection report, passing or failing, through The Compliance Engine. Kitchen hood suppression and kitchen hood exhaust cleaning are both tracked. The provider pays a filing fee when it submits.

Where a hood cleaning report has to go through The Compliance Engine (Sugar Land, Fort Bend County, and Harris County above), make sure your cleaner files it. If they don’t, the fire marshal’s system can show your kitchen as overdue even when the hood is clean. The per-report fee is the provider’s cost, so ask whether it shows up as a line item on your invoice. Nashville’s suburbs (Brentwood, Gallatin) and Kansas City’s (Independence, Olathe) use the same kind of third-party filing. Katy, League City, Baytown, The Woodlands and other cities were not checked. Confirm with your own fire marshal.

Vet checklist

Open listing slots

Unverified until docs in — Slot 1
Unverified until docs in — Slot 2
Unverified until docs in — Slot 3
Unverified until docs in — Slot 4

Sources

Related guides

Request a listing — company, metro, certs, insurance, service area, photo-report policy.

Get quotes from local hood cleaners

Tell us about your kitchen and we'll pass the request to up to 3 local providers in Houston. No cost to you, no obligation.