What “bare metal clean” means in practice
Every quote promises “cleaned to bare metal.” Fire marshals listen for it; insurers look for it on the written report. Operators often never see it defined. Secondary industry explainers of NFPA 96 (2024 edition) §12.6.5 treat it as an outcome: accessible exhaust surfaces cleaned until the underlying metal is visible — not a canopy wipe, not “degreased,” and not a polished hood face with a greasy plenum behind it. This page is a facilities check for verifying that outcome without inventing prices or guarantees.
Outcome vs marketing language
| Phrase on the quote | What operators should check | Usually fails when… |
|---|---|---|
| “Cleaned to bare metal” | Metal visible; reflective under flashlight; seams/corners match flat panels | Uniform dull film left; corners dark while flats look clean |
| “Degreased” / “serviced” | Method words — ask for the bare-metal outcome and photos | Chemical applied, rinse incomplete, residue remains |
| “Hood cleaned” | Ask: canopy only, or plenum + duct + fan? | Visible canopy wipe; ducts and fan skipped |
| “Full system” | Panel openings tagged; fan hinged/opened; report lists each surface | No panel tags; 90-minute visit on a multi-hood path |
| “Looks new” | Not required — old steel can be bare metal with heat stain/patina | Confusing factory finish with grease removal |
Secondary Facilitec note: NFPA specifies the result, not the cleaning method. Grease is opaque; bare metal reflects. A glove test and a flashlight are the field checks AHJs use.
Surface-by-surface (accessible portions)
| Surface | Bare metal looks like | Common miss |
|---|---|---|
| Hood canopy interior | Seams, rivets, and flats all clear | Flats wiped; corners left |
| Plenum (behind filters) | Reflective metal; grease trough empty | Filters washed; plenum film left |
| Horizontal duct | Panel opened; interior scraped/washed; flashlight reflection | “Cleaned what we could reach” with no panels opened |
| Vertical riser | Access at levels; base cleanout emptied | Top or bottom only |
| Exhaust fan interior | Wheel blades show metal; housing and drain clear | Housing exterior wiped; blades coated |
| Filters | Operator daily/weekly job — separate from §12.6.5 fixed-path clean | Treating staff filter wash as the deep clean |
Credible bare-metal job
- Quote names hood + plenum + ducts + fan
- Written report lists surfaces cleaned and inaccessible areas with reasons
- Before/after photos: plenum, at least one duct opening, fan wheel
- Service label notes exclusions honestly
- Access-panel tags where panels were opened
Red flags
- “System cleaned” with no surface detail
- Label with zero exclusions on a known dead-end duct
- Photos of shiny canopy only — no duct/fan
- In-and-out visit far shorter than system size allows
- Confusing grease-depth gauge talk with “we left a film on purpose”
Field note — inaccessible ≠ “done”
- Secondary §12.6.5 applies to accessible portions. Secondary §12.6.4 expects the system to be made accessible (panels, fan hinge) where it is not.
- Honest label language: “vertical riser above second floor — no access; panel recommended” is useful. A blank exclusions line on that same system is not.
- FindHoodCleaner / Summit secondary notes: report should name areas cleaned and areas not cleaned with reasons; photos of bare metal are the operator’s fastest verify.
- Grease-depth gauges (inspection) and bare-metal outcome (cleaning) answer different questions — see the grease-depth thresholds guide.
Operator verification checklist
- Pull one filter after the job — flashlight into the plenum; look for reflection and a clean trough.
- Read the written report — surface-by-surface findings, not one sentence “hood system cleaned.”
- Demand path photos — plenum, duct through a panel, fan wheel; timestamped if the vendor offers it.
- Check the service label for exclusions — match against known missing panels or lift-off-only fans.
- Confirm panel tags — opened panels should show who/when (secondary §12.6.10 pattern).
- Compare time to system size — secondary industry timing notes: a full single-hood moderate kitchen is commonly multi-hour work, not a rushed canopy pass.
- Keep the file together — label + tags + report + photos for AHJ and insurer (see cleaning report checklist).
Who it’s for / not for
- For: kitchen managers comparing quotes that all say “bare metal”; multi-unit operators standardizing report language; anyone who got a canopy wipe that failed inspection
- Not for: claiming a specific NFPA section number for your city without checking the adopted edition; inventing photo-count requirements; chemical/runoff rules (use the runoff guide); legal advice
Sources
- Facilitec Southwest — “Cleaned to Bare Metal” / NFPA 96 §12.6.5 (secondary explainer; outcome standard, surface table, verification)
- FindHoodCleaner — professional hood cleaning before & after (secondary; bare-metal visual checks, photo/sticker expectations)
- Summit Facility Solutions — NFPA 96 hood cleaning guide (secondary; path coverage + areas-not-cleaned documentation)
- FindHoodCleaner — hood cleaning myths (secondary; canopy-only vs full path)
- US Made Supply — NFPA 96 overview (secondary; inaccessible areas / documentation notes)
- HoodFilters — NFPA 96 reference excerpts (secondary manufacturer summary; verify against your adopted edition)
- Total Food — exhaust hood cleaning FAQ (secondary; industry “bare metal” language + Grease Gauge mention)
Next step
On the next clean, require three photos (plenum, one duct opening, fan wheel) and a report line for any inaccessible section. Walk the plenum with a flashlight before you sign off. If panels or a fan hinge are missing, treat that as a work order — not a forever excuse. Confirm wording against your AHJ’s adopted edition; this page is secondary, not legal advice.