Guide
Grease depth thresholds explained (secondary-sourced; verify NFPA)
Inspection cadence and cleaning trigger are different jobs. Secondary NFPA 96 explainers say Table 12.4 sets how often someone measures grease; Section 12.6.1.1 sets how much grease forces a clean. Operators often hear “one-eighth inch” as a universal rule — secondary sources say that number is the fan-housing threshold, not the whole system. Numbers below are secondary summaries. Buy or cite the edition your AHJ adopted; this is not the official text and not legal advice.
Secondary threshold table
| Where (secondary framing) | Depth (secondary) | Rough feel | Cited section (secondary) |
|---|---|---|---|
| Hoods, grease-removal devices (filters), fans, ducts | 0.002 in / 50 μm | ~ copy-paper thickness | §12.6.1.1.1 |
| Other surfaces (non–fan-housing) | 0.078 in / 2000 μm | ~ US nickel thickness (secondary analogy) | §12.6.1.1.3 |
| Fan housings | 0.125 in / 3175 μm | 1/8 in (~ two dimes stacked, secondary analogy) | §12.6.1.1.4 |
Micron note: secondary sources use 3175 μm for 0.125 in — not the informal “3250” sometimes seen in shorthand. Always prefer the inch figure plus your edition’s text.
How the measurement works (secondary)
- Secondary §12.6.1.1.2: place a grease depth-gauge comb on the surface — opinion is not the method
- Inspection happens on the Table 12.4 cadence (solid monthly / high quarterly / moderate semiannual / low annual — secondary summaries)
- Cleaning is required when the applicable depth is observed — not automatically on every inspection in every kitchen
- Secondary §12.6.2 also frames a “clean before heavily contaminated” intent alongside the measured triggers
- Who measures: properly trained, qualified, and certified person acceptable to the AHJ (secondary §12.4 / §12.6.1)
Field note — framing variance to watch
- Some secondary explainers treat 50 μm / 0.002 in as the cleaning-required limit on hoods/filters/fans/ducts
- Others treat 50 μm as the clean-to / acceptable target after cleaning, and emphasize 2000 μm / 0.078 in as the “cleaning required” notch on surfaces, with 3175 μm / 0.125 in reserved for fan housings
- Both camps agree the popular “1/8 inch everywhere” shorthand is wrong for ducts and hoods
- Do not litigate millimeters from a blog — open the edition your AHJ named on the notice
2027 edition: the depth rules move into the inspection section
NFPA now lists the 2027 edition of NFPA 96 as current (NFPA 96 document page). A supplier summary reviewed in July 2026 puts issuance at April 24, 2026, effective May 14, 2026, and says the edition “updates the grease buildup inspection section” (Pro Fire and Safety, secondary). What that update looks like is visible in NFPA’s public first-revision report for the cycle — proposed text, not the final printed standard (FR report, First Revision No. 52):
| Item | 2024 numbering (being moved) | First-revision proposal for next edition |
|---|---|---|
| Depth-gauge comb on the surface | §12.6.1.1.2 (cleaning section) | §12.4.1 (inspection section); Figure 12.4.1 adjusted to show which part of the rule each comb depth goes with |
| 0.078 in / 2000 μm | §12.6.1.1.3 — “Where a measured depth of 0.078 in. (2000 μm) is observed, the surfaces shall be cleaned” | §12.4.2 — adds “on a surface other than in fan housings” |
| 0.125 in / 3175 μm | §12.6.1.1.4 — fan housings | §12.4.3 — fan housings; same number |
Committee statement (VEN-AAA, submitted Sept 16, 2024): “The requirements for grease depth have moved from the cleaning section of chapter 12 to the inspection section.” The numbers did not change. What changed is where they sit — the reading is now framed as part of the inspection itself, and the 0.078 in line now says plainly that it is the non–fan-housing limit. That settles half of the framing argument above. It does not settle the 0.002 in / 50 μm figure: FR-52 does not touch it, so keep treating 50 μm as a secondary summary until you read the adopted text.
Field note — other first revisions an inspect-only visit now has to meet
- FR-10 / §12.6.9: access panels and cover plates restored “upon completion of exhaust system inspection or cleaning” — not just after a clean. Committee: panels should be restored “whenever they are removed”
- FR-12 / §12.6.12: electrical switches and system components returned to an operable state after an inspection too
- FR-11 / §12.6.10: company label near any access panel removed and reinstalled, dated for the inspection or cleaning
- FR-13 / new §12.6.17.1: metal grease-drip containers that are missing, broken, distorted, or leaking shall be replaced — see grease cup / containment at the rooftop fan
- Your AHJ may still enforce 2024 (or older) numbering. A supplier reference page still tells operators the 2024 edition remains enforceable until the AHJ adopts the new one (Facilitec Southwest). Same numbers either way; cite the section from the edition on your notice
Operator use that holds up
- Ask the inspector where they measured and which threshold they applied
- Require the written report to list inaccessible areas instead of silent skips
- Budget cleaning at every inspection for solid-fuel / high-volume (secondary operational reality)
- Keep the depth reading (or photo of the comb) with the visit file when provided
Common misunderstandings
- “We’re under 1/8 inch on the canopy — we’re fine” (wrong surface / wrong number)
- Eyeballing grease instead of a gauge
- Confusing inspection sticker cadence with automatic cleaning
- Treating a secondary blog table as the legal text
How this ties to scheduling
| Cooking tier (secondary Table 12.4) | Inspect | Practical cleaning plan (secondary) |
|---|---|---|
| Solid fuel | Monthly | Plan a clean nearly every cycle — creosote + grease load fast |
| High volume (24-hour, charbroil, wok) | Quarterly | Usually clean at the same visit — 0.002 in is easy to cross |
| Moderate volume | Semiannual | Inspect on schedule; clean when depths trip |
| Low volume (church, seasonal, senior) | Annual | May pass without a clean some years — still need the written report |
Who it’s for / not for
- For: managers who heard “1/8 inch” and want the three-number split; anyone reading a deficiency that cites depth; facilities leads training staff what “clean when measured” means
- Not for: substituting this page for the official NFPA text, DIY AHJ arguments, or inventing local amendments
Sources
- Facilitec Southwest — how often to clean (2026 NFPA 96 guide) (secondary; three-threshold table, paper/nickel/dime analogies, inspection vs cleaning split)
- Facilitec Southwest — NFPA 96 codes reference (secondary; §12.6.1.1.1 / .1.1.3 / .1.1.4 framing; “1/8 in is fan-housing-only” note)
- Cleaning Pros Plus — NFPA 96 certificate / grease levels (secondary; comb method; 50 / 2000 / 3175 μm ladder; clean-to vs cleaning-required framing)
- NFPA first-revision / committee PDF excerpt (public docinfo) (FR-52 moves comb + 0.078 in / 2000 μm + 0.125 in / 3175 μm from §12.6.1.1.2–.4 to §12.4.1–12.4.3; FR-10 / 11 / 12 / 13 inspection-visit and grease-container edits — proposed text, not a substitute for your adopted standard)
- TFP1 — NFPA 96 cleaning frequency (secondary; inspection cadence overview used elsewhere on this site)
- NFPA — NFPA 96 document information (lists 2027 as the current edition)
- Pro Fire and Safety — 2027 NFPA updates for commercial kitchens (secondary; NFPA 96 issued 4/24/2026, effective 5/14/2026; grease buildup inspection section updated; AHJ adoption caveat)
Next step
At the next inspection, ask the tech to show the comb reading and name which surface threshold they used. Put that line on the written report. If a deficiency cites “1/8 inch” on a hood or duct, ask which section of your adopted edition they mean — then verify against the official text, not this page.