Changing your menu or cooking equipment: when the cleaning schedule changes

Updated 2026-10-11

The exhaust inspection interval is set by what you cook, not by what the last tenant cooked or what the service contract says. Add a charbroiler, put a wok station on the line, bring in a wood-fired oven, or start staying open all night, and the fire code interval can drop from six months to three, or to one. Swapping or moving equipment under the hood can also pull in the suppression contractor, the mechanical engineer, and the sewer utility.

Short answer Before the new item goes on the line, tell three people: your hood cleaner (new interval), your suppression contractor (nozzle coverage and UL 300 status), and whoever designed or permits your hood (exhaust capacity and makeup air). Charbroiling, wok cooking, and 24-hour cooking move you to a 3-month interval; solid fuel moves you to 1 month. Moving or replacing appliances under a hood means the suppression design gets re-checked, and an older system that isn’t UL 300 listed has to be upgraded. Cutting the menu back doesn’t move you to the 12-month row unless you’re a low-volume operation or the fire code official approves it.

What each change does

ChangeInspection interval (IFC Table 606.3.3.1)Other work it can trigger
Add a charbroiler or char grill3 months (high-volume: charbroiling)Suppression nozzle added or re-aimed; check the hood is listed and sized for the heavier appliance
Add a wok station3 months (high-volume: wok)Suppression coverage; wok burners are high heat and high exhaust (wok line exhaust)
Go to 24-hour service3 months (high-volume: 24-hour)Cleaning windows get harder to book; plan the overnight shutdown (24-hour planning)
Add a wood, charcoal, or pellet appliance1 month (solid fuel)NFPA 96 has its own chapter for solid fuel cooking (Chapter 15) with separate exhaust and spark arrester rules; creosote as well as grease (solid fuel reality check)
Swap fryers or griddles like for likeNo change if the cooking type stays the sameReplacing cooking equipment is a UL 300 trigger for older suppression systems; nozzle positions re-checked
Move appliances along the lineNo change by itselfRepositioning is a UL 300 trigger; nozzles are placed per appliance, so coverage must be re-verified
Switch from animal fat to vegetable oilNo change by itselfA UL 300 trigger for older dry or wet chemical systems
Cut the menu, fewer hoursStays 6 months unless you fit the low-volume row (places of worship, seasonal businesses, senior centers) or the fire code official approves another intervalGet any approved change in writing and keep it in the binder

The interval rows above come from the 2024 IFC as adopted by Denver; other editions and NFPA 96 (Table 12.4 in recent editions) use the same four categories. Your fire marshal decides which row you’re in. See how often to inspect.

The suppression system: re-evaluate and maybe upgrade

The hood, duct, and makeup air

The grease interceptor

Sewer utilities size interceptors partly from the kitchen equipment. Denver’s grease interceptor policy (DOTI Right-of-Way Services Policy 14.0, effective January 5, 2026) builds its sizing method around fixtures and equipment such as a grill or wok stove, a two-basket fryer, and an oven. More fryers usually means more pumping, and in some cities a bigger interceptor. In Tampa, expanding an existing food service facility makes it a “new” facility under the city’s Grease Management Ordinance (City Code §26-306(b)(1)), which means a trap or interceptor installed to the current Florida plumbing code. Call the utility before a major line change. See grease trap service and hood day.

Checklist before the new equipment goes in