Makeup air and exhaust balance — when to call HVAC not a cleaner

Updated 2026-09-26

A greasy duct can starve capture. So can a kitchen that has no makeup air, a dead makeup-air unit (MAU), or a defeated interlock. Hood cleaners remove grease to bare metal along the exhaust path. They do not size, balance, or commission the supply that replaces what the fan pulls out. This page is the split: symptoms that point to exhaust/makeup imbalance, who to call, and what to ask before you pay for another clean that cannot fix the door slam. For grease-path scope see full-system vs canopy-only; for fan hardware see the hinge checklist.

Short answer Secondary sources republishing IMC §508.1 require makeup air whenever commercial kitchen exhaust runs, approximately equal to total exhaust, with mechanical makeup starting and operating with the exhaust. Secondary NFPA 96 §8.3.1 (SEFA / trade republish) caps negative pressure in cooking areas at about 0.02 in. w.c. (4.9 Pa). Hard-to-open or slamming doors, smoke rolling the hood lip, dining-room odor, cold drafts at the line, or a MAU that does not run with the fan are balance/HVAC problems — call a commercial HVAC or TAB tech for measured CFM and pressure, not another canopy wipe. Your AHJ’s adopted IMC/NFPA edition wins; confirm section numbers locally.

Symptoms → who to call

What you see / feelLikely cause (field pattern)Who to call
Exterior / kitchen doors hard to open or slam shut Exhaust pulling more than makeup returns — room goes hard negative HVAC / TAB — measured balance; check MAU on, filters, dampers, interlock
Smoke / grease vapor rolls out the hood face with fans “on” Capture starved by negative pressure, wrong makeup throw into the capture zone, or fouled duct raising static First: confirm duct/fan were cleaned to bare metal. If clean and still spilling → HVAC/TAB
Cooking odor in dining / adjacent spaces Kitchen pushed positive (too much makeup) or transfer paths wrong HVAC/TAB — pressure kitchen-to-dining, not a cleaner
Line freezing in winter; staff prop the back door Untempered or mis-set MAU discharge; door prop then wrecks the balance HVAC — MAU heat/discharge setpoint (IMC secondary ~10°F differential)
MAU silent while exhaust fan runs Defeated or failed interlock; separate switch; relay fault HVAC / controls — prove fans start/stop together
Heavy grease in duct / fan / grease cup; canopy looks dirty Cleaning cadence or incomplete scope Hood cleaner — full system, not HVAC first
Fan won’t spin, belts shredded, hinge seized Mechanical exhaust hardware Cleaner (reinstall) + HVAC/electrician as needed; see hinge / post-clean checks

Secondary code notes (verify edition)

Source (secondary)What it says in plain termsOperator takeaway
IMC §508.1 (ICC Building Safety Journal / SEFA republish) Makeup air required while commercial kitchen exhaust operates; quantity from all sources approximately equal to exhaust; mechanical makeup starts and runs with exhaust; makeup must not kill hood capture Ask HVAC to prove interlock and measured makeup ≈ exhaust — not a verbal “it should be fine”
IMC §508.1.1 (ICC / SEFA) Temperature difference between makeup and conditioned space ≤ about 10°F unless HVAC can carry the load (compensating-hood exception exists) Cold blast at the line is a tempering/setpoint problem, not a cleaning ticket
NFPA 96 §8.3.1 (SEFA secondary excerpt) Replacement air adequate so negative pressure in cooking areas does not exceed 0.02 in. w.c. (4.9 Pa) Door slam + smoke spill often sit past that limit — need a manometer, not a mop
UMC §511.3 (SEFA secondary) Same 0.02 in. w.c. negative-pressure cap framing where UMC is adopted Confirm whether your city uses IMC, UMC, or a hybrid

Section numbers move by edition and local amendment. Treat the cites above as pointers from secondary republishers, then verify with the AHJ and the engineer of record.

Hood cleaner scope (grease path)

  • Clean hood, filters, plenum, ducts, fan housing to bare metal
  • Report inaccessible sections; restore panels; service label
  • Reinstall fan, check spin/belts as part of job closeout (see post-clean guide)
  • Flag MAU-off / door-slam symptoms on the report — do not “fix” balance

HVAC / TAB scope (air balance)

  • Measure exhaust CFM, makeup CFM, kitchen-to-dining and kitchen-to-outdoors pressure
  • Prove MAU–exhaust interlock both directions
  • MAU filters, belts, dampers, burner/discharge temperature
  • Correct throw locations that blast the hood capture zone
  • Written balancing report after fan or MAU replacement

Operator checklist before you call

Field note — why “bigger fan” often makes it worse

Who it’s for / not for

Sources