Directory · Los Angeles

Los Angeles commercial kitchen hood cleaning

Research index for operators. Public rules we found, how to vet a cleaner, open listing slots. Not a ranked vendor list.

No LA-only cleaning interval: We found no city-specific hood-cleaning cadence or city roster of licensed hood cleaners. The inspection intervals below come from the statewide California Fire Code that the LA Fire Code is built on. Confirm with LAFD (city) or LA County Fire (unincorporated areas and contract cities) for your address.

LAFD · California Fire Code Table 606.3.3.1 · LA County Environmental Health · LA Sanitation FOG permit · FOG ≠ exhaust · Suppression §904.13.5 · OCFA D-02 · San Diego Fire-Rescue · LAFD + County Fire fees · Updated 2026-11-08

Which fire code applies

Inspection intervals (California Fire Code §606.3.3.1)

Hoods, grease-removal devices, fans, ducts, and other appurtenances are inspected by qualified individuals at the intervals in Table 606.3.3.1, or as approved by the fire code official. Cleaning follows when the inspection finds grease buildup.

Type of cooking operationInspection frequency
Solid fuel-burning cooking appliances (wood, charcoal)1 month
High volume, such as 24-hour cooking, charbroiling, or wok cooking3 months
All other cooking operations6 months
Low volume, such as places of worship, seasonal businesses, senior centers12 months

Owner and health-inspection rules

Grease interceptors (City of Los Angeles)

Suppression service runs on its own six-month clock

Hood cleaning and the wet-chemical suppression system are two different jobs, often two different companies. The California Fire Code sets the suppression schedule separately from the cleaning table above.

Many kitchens book the hood cleaning right before a suppression visit so the technician checks nozzles and links on a clean system. See who does which job, fusible links, and nozzle caps after cleaning.

What LAFD and LA County Fire charge

Hood cleaning itself carries no city or county fee. The money shows up around it: the annual fire permit for a dining room, the plan check when a suppression system goes in or moves, and the bill for a return visit when a correction isn't done. Which schedule you pay depends on who covers your address.

ItemCity of Los Angeles (LAFD)LA County Fire (unincorporated + contract cities)
Annual fire permit, restaurant or bar with 50+ occupantsA-2 Food/Drink Assemblage: $764 (50–99), $1,146 (100–499), $1,528 (500+), paid to the Office of Finance; rates effective 9/13/2025Annual assembly inspection: $390 under 12,500 sq ft, $488 for 12,501–25,000 sq ft, up to $780 over 75,000 sq ft
Commercial kitchen hood suppression (UL 300) plan reviewFire/life safety plan review: the greater of 0.111% of project value or $1,011$293 per plan review
Hood system field inspection$337 per hour, inspection and re-inspection$390 per inspection
Extra visits$337 per hour; off-hours $480 for the first 4 hours, then $120 per hour, plus the hourly inspection rate$98 for each inspection after the initial one and one reinspection

Outside the City of Los Angeles

The same statewide table applies across Southern California, but the office that enforces it changes with your address. Unincorporated areas and many contract cities in LA County are served by LA County Fire. Orange, Ventura, Riverside, San Bernardino, and San Diego counties each have county fire agencies, and many cities there run their own fire departments with local amendments. Call the fire prevention office for your address and ask two things: which code edition your last inspection used, and whether they want cleaning reports or suppression certificates sent to them or a reporting portal.

Orange County: what OCFA puts on the plan

Most Orange County cities contract fire prevention to the Orange County Fire Authority (OCFA). Its guideline D-02, Fire Extinguishing Systems for Commercial Cooking Operations (2025 edition), is the sheet your hood contractor and suppression installer will be working from. The parts that matter on cleaning day:

Adding or changing a hood suppression system in OCFA territory needs its own Hood & Duct Extinguishing System plan (OCFA plan type PR335), not just the mechanical hood plan. OCFA's plan review fee for that submittal: Unknown (not confirmed from an OCFA fee schedule). Cities with their own fire departments (for example Anaheim, Fullerton, Huntington Beach, Newport Beach, Orange) are not covered by D-02; ask that city's fire prevention office which interval table and forms it uses.

City of San Diego: what Fire-Rescue charges and checks

Inside the City of San Diego, fire inspections are done by Deputy Fire Marshals in San Diego Fire-Rescue's Community Risk Reduction Division. The city's fire code carries the same Table 606.3.3.1 as the rest of California (monthly for solid fuel, 3 months for high-volume, 6 months for other cooking, 12 months for low-volume), with grease found on inspection cleaned to ANSI/IKECA C10 and records kept showing who inspected, who cleaned, and when.

Unincorporated San Diego County and the Deer Springs district are inspected by the County Fire Marshal instead, and cities such as Chula Vista, Oceanside, Escondido and Carlsbad run their own fire prevention offices; ask that office for its fee schedule.

Before you call for a quote

Vet checklist

Open listing slots

Unverified until docs in — Slot 1
Unverified until docs in — Slot 2
Unverified until docs in — Slot 3
Unverified until docs in — Slot 4

Sources

Related guides

Request a listing — company, metro, certs, insurance, service area, photo-report policy.

Get quotes from local hood cleaners

Tell us about your kitchen and we'll pass the request to up to 3 local providers in Los Angeles. No cost to you, no obligation.