Fusible links and detection devices: who replaces them and how often

Updated 2026-10-13

Those small metal links in the hood and at the duct entrance are the automatic heat detectors for most wet-chemical systems. Grease coats them. Heat ages them. Leaving last year’s links in place is a common inspection finding — and it is a suppression job, not a grease-clean job. This page is the operator split: cadence, who may touch them, and what belongs on the service tag.

Short answer Secondary NFPA 96 text (and NFPA 17A) requires metal-alloy fusible links — and metal-alloy automatic sprinklers used as detectors — to be replaced at least semiannually. Replacement elements must be listed and match the temperature rating unless readings justify a change. Year of manufacture and installation date go on the system inspection tag; removed links are destroyed. Bulb-type detectors and non-metal-alloy fusible links are examined and cleaned or replaced at least annually. Fire-damper fusible links on the exhaust path are also replaced at least semiannually by a certified person acceptable to the AHJ. The hood cleaner protects links during a clean; a licensed fire-protection technician does the replace-and-tag work. See suppression vs hood cleaning.

Replacement schedule (secondary NFPA 96 / 17A)

DeviceTypical requirement (secondary)Who
Metal-alloy fusible links on the extinguishing systemReplace at least every 6 months (NFPA 96 §12.2.4 pattern)Licensed / factory-trained suppression tech
Metal-alloy automatic sprinklers used as detectorsSame semiannual replace ruleSuppression tech
Bulb-type detectors / non-metal-alloy fusible linksExamine and clean or replace at least annuallySuppression tech
Fusible links on fire damper assembliesReplace at least semiannually (or sooner as needed) by a certified person acceptable to the AHJPerson your AHJ accepts for damper work — confirm locally
High-volume / heavy grease kitchensCode minimum is still 6 months; trade practice often replaces sooner when grease load is highAsk your suppression contractor; do not invent a shorter legal interval without AHJ direction

Semiannual ITM of the extinguishing system also tests actuation and control components (manual pulls, detectors, actuators). Fusible-link replacement is part of that visit, not a kitchen-staff chore between cleans.

What must be on the tag

Count links the way the listing expects: typically one over each protected appliance plus detection at the exhaust duct entrance (secondary NFPA 17A appliance/duct placement). Exact count is on the system drawings and the last ITM report — ask for that sheet if the invoice looks short.

Hood cleaning day vs suppression day

TaskHood cleanerSuppression contractor
Protect nozzles and links from chemicals / impact during cleanYes — cover and restore—
Replace metal-alloy fusible links on scheduleNoYes
Recharge cylinder after discharge; re-tag systemNoYes
Grease clean of hood, filters, ducts, fanYesNo (not their scope)
Verify nozzles capped and aimed after a cleanRestore what they moved; many kitchens still want suppression tech verifyFinal word on detection line and listing

If the cleaner reports grease-caked links or a missing link, stop cooking under that hood until the suppression contractor replaces and re-tags. A cleaning sticker does not replace a suppression tag. See post-clean checks and night-before prep.