Smoke not pulling into the hood: troubleshooting before calling a vendor

Updated 2026-10-13

The fan is humming and the line is still smoky. That is not automatically a dirty duct. Capture is a chain: air enters at the hood lip, passes the filters, travels the duct, leaves at the fan, and an equal volume has to enter the kitchen as makeup air. Any broken link can leave smoke rolling the lip while the motor still spins. Walk the cheap checks before you book the wrong trade.

Short answer Open an exterior door or window while the line is running. If smoke clears, the exhaust path is moving air and the kitchen is starving for makeup air — call HVAC / TAB, not another canopy wipe. Secondary IMC §508.1 / NFPA 96 §8.3.1 summaries require makeup approximately equal to exhaust and keep cooking-area negative pressure around 0.02 in. w.c. Next: pull a filter (loaded, wrong size, or installed backward); check belts, rotation, and hinge access on the rooftop fan; then book a full-system clean if the plenum, duct, or fan housing is grease-loaded. Filters must stay listed (UL 1046) and in place whenever grease-producing equipment runs (Philadelphia Fire Code §607.3.1 pattern; NFPA 96 grease-removal rules).

Five-minute triage (in order)

CheckWhat you look forIf yes — first call
Door / window testSmoke clears when you open an exterior door or window with the hood runningHVAC / TAB — makeup air or building pressure. See makeup air balance
Filters in place and listedMissing filters, mesh-only in a hood that needs baffles, or filters not UL/ETL stampedStaff replace with listed filters; cook only with filters seated. See filters clean vs replace
Filter load / orientationHeavy grease cake; filter put in backward or wrong size after a wash nightStaff wash/replace; if smoke started right after a filter change, re-seat and size-check first
Fan running but weakBelt shredded or loose; wheel won’t free-spin with power locked out; reverse rotation after electrical workHVAC / sheet metal for belt, motor, rotation. See belt and bearing checks
Grease in the pathPlenum behind filters coated; fan housing heavy; long uncleaned ductHood cleaner for full-system clean with rooftop photos — not canopy-only. See full-system vs canopy
One station onlySmoke escapes at one appliance; rest of the line capturesGeometry / overhang / equipment change — may need hood or appliance move, not just CFM. See menu/equipment changes
Drafts at the lipSupply diffuser blasting across the hood face; pass-through door draftsHVAC to relocate or throttle supply; high-velocity makeup near the hood can push smoke out before capture

What “the fan is on” does not prove

Who to call (split the jobs)

Symptom clusterTradeNot who
Door slam; smoke clears with door open; MAU dark or damper closedCommercial HVAC / TAB (measured CFM and pressure)Not another grease clean alone
Filters packed; plenum/duct/fan greasy; overdue intervalHood / exhaust cleaner acceptable to your AHJNot a pressure-washer who only does the canopy
Belt, bearings, motor, reverse rotation, curb/hingeHVAC / sheet metal / listed fan installerNot the grease-trap pumper
Suppression discharged or nozzles disturbed during troubleshootingLicensed suppression tech before cooking resumesNot kitchen staff resetting the system. See suppression vs cleaning

Operator checklist before you pick up the phone