A cookline flare-up that trips suppression — or worse, enters the plenum — is not a normal hood day. Secondary post-fire guidance is consistent on the sequence: people and 911 first, do not DIY a duct fire, do not scrub the exhaust before the fire marshal releases the scene, then get the right vendors in the right order. This page is operator triage after the event is controlled: who to call, what not to touch, and what to document before you cook again. For the split between wet-chemical work and grease cleaning, see suppression system vs hood cleaning.

Short answer If fire is active or anyone is at risk: evacuate, activate suppression / shut fuel if safe, call 911 — do not chase flames into the duct with a portable extinguisher. After the scene is safe and responders have control: notify the carrier promptly, pull your hood file, get on the suppression vendor’s and exhaust cleaner’s calendars — but do not deep-clean the exhaust until the AHJ releases it (it is evidence). Reopening typically needs AHJ clearance, suppression recharge/retag by a licensed fire-protection contractor, full-path exhaust cleaning to bare metal with a written report, and carrier authorization for repairs. Not firefighting, legal, or insurance advice.

Safety first (before any “emergency clean”)

Who to call — and in what order (after control)

PartyWhenWhat they doWhat they don’t do
911 / fire department Active fire, smoke in duct/roof, injuries, or doubt Suppress, investigate, declare scene status Not your long-term cleaning contractor
AHJ / fire marshal After responders; before you deep-clean or reopen Investigation, scene release, deficiency list, reopen approval Does not recharge Ansul or degrease ducts
Licensed suppression contractor Any discharge (or failed discharge) Inspect, recharge, replace links/nozzles as needed, retag, verify fuel shutoff Not a substitute for full exhaust grease cleaning
Qualified exhaust / hood cleaner After AHJ release (secondary: often after or coordinated with suppression work) Full-path clean toward bare metal; photo + written report; flag heat damage Does not reset/recharge the wet-chemical system; does not fabricate duct
Insurance carrier / broker Prompt notice (secondary: often 24–72 hours) Claim number, adjuster requests, repair authorization Does not clear the AHJ inspection
Mechanical / roofing (if needed) When cleaner flags warped duct, failed seams, damaged fan, roof curb heat Repair/replace damaged path Not the same PO as a routine hood clean

Secondary Facilitec framing: four sign-offs before cooking again — AHJ release, suppression recertification, exhaust cleaned and documented, carrier authorization for repairs. Sequence matters more than speed. Food Service Nerd (secondary): you do not reset suppression yourself after a discharge.

First 24 hours — operator checklist

After release — defensible reopen path

  • AHJ written release / deficiency list in hand
  • Suppression vendor recharges, tests, retags — licensed fire protection
  • Exhaust cleaner does full path (hood → duct → fan), bare-metal target, photos + report
  • Heat-damaged sections handed to mechanical; roof to roofing if needed
  • Carrier authorizes spend before you rebuild the duct
  • Cooking stays off until AHJ says resume

Moves that create problems

  • Staff “emergency wipe” of the hood before marshal release
  • DIY suppression reset or cooking on a discharged system
  • Canopy-only clean and calling it post-fire ready
  • Assuming the cleaner will also retag Ansul
  • Reopening on manager say-so without AHJ / vendor clearances
  • Fighting a duct fire with a portable extinguisher

Field note — flare-up vs duct involvement (secondary timelines)

Documentation to gather for the claim and reopen

If you are choosing a new exhaust vendor after a citation or fire, use choosing a vendor after an AHJ violation for the process — not the legal theory.

Who it’s for / not for