Guide

Used cooking oil pickup vs hood vendor — different jobs

Updated 2026-09-30

Used cooking oil (UCO / yellow grease) pickup is not hood cleaning, and it is not grease-trap pumping. One hauls spent fryer oil from a dedicated container for recycle. One cleans airborne grease deposits in the canopy, duct, and fan under fire-code / NFPA 96 rules. One pumps waterborne FOG from an interceptor under municipal pretreatment / FOG programs. Operators get burned when a “full grease service” pitch collapses those three into one invoice line. For trap vs hood same-day coordination, see combining grease trap service with hood day. For hood wash-water path questions, see chemical runoff and grease waste handling.

Short answer Treat yellow grease recycle, interceptor FOG pump-out, and exhaust cleaning as three contracts — even if one company holds credentials for more than one. EPA’s food-service FOG fact sheet separates yellow grease (point-of-use collection for consolidation / reuse) from grease-trap waste that must stay out of the sewer. A hood cleaner’s NFPA report does not document fryer-oil pickup. A UCO manifest does not prove the exhaust path was cleaned. A trap pump ticket does not cover either. Ask for the license that matches each stream, keep each paper trail, and never pour cooled fryer oil into a sink or interceptor to “save a pickup.”

Three grease paths — keep them separate

PathWhat it handlesTypical vendorWho usually regulatesTypical proof
Kitchen exhaust (hood / duct / fan) Airborne grease vapor and deposits on the cookline path Exhaust / hood cleaning contractor Fire marshal / AHJ (NFPA 96 / fire code) Inspection/cleaning report, hood service label, path photos
Grease trap or interceptor (brown grease / FOG) Waterborne FOG from sinks, dishwash, floor drains — mixed with wastewater and solids Licensed FOG hauler / pumper Wastewater utility / municipal FOG program; often health on logs Pump-out / trip-ticket manifest; retention per local FOG rules
Used cooking oil (yellow grease) Spent fryer / cooking oil collected at point of use before it hits a drain — recycle commodity Oil recycler / consolidation / rendering collector State / local used-oil or rendering rules (varies); not the same credential as trap hauling in many states Collection / recycle manifest or ticket; locked container program

EPA’s National Pretreatment Program fact sheet: FOG captured on-site is generally classified into yellow grease (used cooking oil and waste greases separated at point of use) and grease trap waste. FSEs often accumulate yellow grease for pickup by consolidation companies for re-sale or re-use (tallow, feed supplements, fuels) and use interceptors to keep FOG out of the POTW. That is sewer / pretreatment language — not a fire-code exhaust clean.

Yellow grease vs brown grease (operator language)

Field note — state examples (verify your AHJ / agency)

What each contract usually covers (and does not)

ContractUsually coversDoes not cover
Hood / exhaust clean Inspection and/or cleaning of hood, filters, plenum, ducts, fan to AHJ / NFPA expectations; report + label Fryer oil recycle; interceptor pump-out; permission to dump wash water to storm drains
FOG / trap pump Evacuation of interceptor compartments (scope must say full pump vs skim); disposal manifest Exhaust path cleaning; yellow grease container service (unless separately credentialed and scoped)
UCO / yellow grease pickup Scheduled or on-call removal from the recycle container; often a locked tank; recycle ticket Trap pump-out; NFPA exhaust cleaning; fixing a clogged sewer lateral

Why “we handle all your grease” can mislead

Healthy bundling pattern

  • Written scopes list each stream on its own line with the matching license / permit number
  • Separate manifests or tickets filed in the binder (hood report · FOG manifest · UCO ticket)
  • Staff SOP: cooled fryer oil → locked UCO container only; never sink / never interceptor
  • Hood wash-water plan still written — trap truck on site does not excuse storm-drain dumping

Red-flag pitch language

  • “Grease service” with no breakdown of exhaust vs trap vs oil
  • “Our hood guy takes the oil” with no recycler credential shown
  • “Trap clean covers the fryer oil” — different waste, different rules
  • One ticket for everything and no way to show the fire marshal the path was cleaned

What to ask before you sign

AskHood cleanerFOG / trap haulerUCO / oil recycler
Scope Full path (hood, filters, plenum, duct, fan) with report + photos? Full pump-out of all compartments + scrape, or skim only? Which container, pickup cadence, indoor caddy vs outdoor locked tank?
Credential Acceptable to local AHJ / fire marshal? Licensed FOG / liquid-waste transporter for this city? State / local used-oil or rendering registration that covers yellow grease?
Paper trail Written report + hood label; who gets the copy? Manifest left on site; retention period? Collection ticket each pickup; who keeps it?
Cross-work claim Do you also haul UCO or pump traps? Show those licenses separately Do you also clean exhaust or collect yellow grease? Show those credentials Do you also pump interceptors or clean hoods? Show those credentials — not a tote logo
Disposal / recycle path Where does wash water / scraped grease go? Receiving facility on the manifest? Renderer / biodiesel / consolidation outlet — and is the container locked against theft?

Operator checklist

Who it’s for / not for

Sources